17.3 ETSTAT (Acquiring Ethernet Unit Information: FTP/HTTP/SMTP)
Execution example
Example 1) When specifying a transfer number
The 7-word status for the transfer number that is specified by [S2] is read.
[S1]... "FTPc" [S2]... "ID5" [D]...DT0
DT0
Control relay
DT1
Execution done code
DT2
Transfer done code
DT3-DT4
Number of successful transfers (individual)
DT5-DT6
Number of failed transfers (individual)
Example 2) When "IDALL" (all ID numbers) is specified
The entire status for all transfer IDs and the status for each ID that is set are read.
[S1]... "FTPc" [S2]... "IDALL" [D]...DT0
Transferring ID
DT0
number
DT1
Transferring data type
DT2
Transfer status
DT3
Transfer result
Latest transfer success
DT4-DT9
time
Latest transfer failure
DT10-DT15
time
Number of transfer
DT16-DT17
successes (Whole)
Number of transfer
DT18-DT19
failures (Whole)
DT20
ID transfer setting
DT21-DT27
Status of ID0
DT28-DT34
Status of ID1
DT35-DT41
Status of ID2
-
-
DT(21+7x)
Status of IDx
-DT(27+7x)
Example 3) When "LOGALL" (all LOG numbers) is specified
The entire status of the logging trace and the status of each ID that is set for the logging trace
are read.
[S1]... "FTPc" [S2]... "LOGALL" [D]...DT0
Transferring ID
DT0
number
DT1
Transferring data type
DT2
Transfer status
17-18
Only the bit for each ID number that is set is turned ON.
The status data (7 words) for each of the 16 IDs is read.
Control relay: 1 word
Execution done code: 1 word
Transfer done code: 1 word
Number of successful executions (individual): 2 words
Number of failed executions (individual): 2 words