17.17 HTTPcSET (HTTP Client Transfer Setting)
Operand [S3] setting (UPDOWN operation for a device)
● Specify the starting address of the device area that stores the string data that indicates
source device settings, or a character constant.
● Downloaded data is stored immediately after uploaded data. The number of acquisitions (the
number of bytes) is stored in the first two words.
Setting
Settings
item
Source device
setting
S3
Number of
transferred data
(number of
bytes)
Maximum
number of
acquisitions
(number of
bytes)
(Note 1)
Input each source device setting parameter separated by a comma ",".
(Note 2)
Specify the operation setting parameters in the order of the above table.
Setting example
Exam
S3
"WX16,32.32"
ple 1
Device setting, Device division: Global, Device code: WX, Device number: 16, Number of bytes:
32 bytes,
Settings
Number of acquisitions: 32 bytes
Exam
S3
"DT123456,250,250"
ple 2
Device setting, Device division: Global, Device code: DT, Device number: 123456, Number of
bytes: 250 bytes,
Settings
Number of acquisitions: 250 bytes
17-92
Specify the source device setting.
● Global devices
Specify device code + device number.
● Local devices
"PB" + PB number + "_" (underscore) + device code +
device number
<Devices that can be specified>
Global devices
WX
WY
WR
WL
DT
LD
Specify the number of transferred data (number of bytes). (1 to
7 digits)
* The number of bytes that can be simultaneously transferred
is 1 MB for all 16 IDs.
Specify the maximum number of acquisitions (number of
bytes). (1 to 7 digits)
* Data can be obtained up to the maximum number of
acquisitions.
* The number of bytes that can be simultaneously acquired is 1
MB for all 16 IDs.
Local devices
WX
WY
WR
WL
DT
LD
WUME-FP7CPUPGR-12
Setting range
1 to 1048576
(1MB)
1 to 1048576
(1MB)