14.10 ACHK (ASCII Data Check)
14.10 ACHK (ASCII Data Check)
■
Ladder diagram
■
Available operation units (●: Available)
Operatio
bit
n unit
i
■
List of operands
Operand
Description
S1
Control string (2 to 16 characters)
S2
Starting number of the area that stores an ASCII code
N
Conversion method
■
Available devices (●: Available)
Operan
d
W
W
X
Y
S1
●
●
S2
●
●
(Note 1)
●
●
N
(Note 1)
To be handled as a 32-bit integer (UL), regardless of operation unit.
■
Outline of operation
● This instruction checks whether the specified ASCII code string can be converted using the
ATOB instruction.
● According to the control characters specified by [S1], this instruction checks whether the
ASCII code stored in the area specified by [S2] can be normally converted using the
conversion method specified by [N].
● If the check result is normal, the system relay SRB turns ON (1), and if abnormal, SRB turns
OFF (0).
● Specify the same value as the ATOB instruction for [S1] the control string, [S2] the beginning
of the source data, and [N] the conversion method.