Panasonic FP7 Series Command Reference Manual page 872

Cpu unit
Hide thumbs Also See for FP7 Series:
Table of Contents

Advertisement

16.3 PMGET (Acquiring MEWNET-W Parameters)
Storag
e
Items
locatio
n
Number of occurrences of synchronous
[D+3]
abnormality
Number of occurrences of transmission
[D+4]
answer NACK
Number of occurrences of three
[D+5]
consecutive transmission answers
NACK
Number of occurrences of transmission
[D+6]
answer WACK
Number of occurrences of three
[D+7]
consecutive transmission answers
WACK
Number of occurrences of non-
[D+8]
response
Number of occurrences of three
[D+9]
consecutive non-response
Number of occurrences of receive
[D+10]
command code error
Number of occurrences of received
[D+11]
data CRC error
Number of absences of received data
[D+12]
end code
Number of occurrences of received
[D+13]
data format error
Number of occurrences of received
[D+14]
data NOT support error
Acquired data (PLC link refresh operation monitoring information): When [S] = 3
Storage
locatio
Items
n
RING counter for the
[D]
number of receptions
Current receive
[D+1]
interval (x 1 ms)
Minimum receive
[D+2]
interval (x 1 ms)
Maximum receive
[D+3]
interval (x 1 ms)
RING counter for the
[D+4]
number of
transmissions
Current send interval
[D+5]
(x 1 ms)
16-12
Range:
Range:
Description
The number of receptions is stored. When the value
U0 to U65535
exceeds 65535, it returns to 0.
-
-
The reception interval is stored.
-
The number of transmissions is stored. When the value
U0 to U65535
exceeds 65535, it returns to 0.
-
The send interval is stored.
Description
WUME-FP7CPUPGR-12

Advertisement

Table of Contents
loading

Table of Contents