Connecting Ac Power To A Mx2020 Router With Three-Phase Delta Ac Power Distribution Modules; Figure 71: Connecting The Grounding Cable - Juniper MX2020 Hardware Manual

3d universal edge router
Hide thumbs Also See for MX2020:
Table of Contents

Advertisement

Related
Documentation
Connecting AC Power to a MX2020 Router with Three-Phase Delta AC Power
Distribution Modules
Copyright © 2013, Juniper Networks, Inc.
Secure the grounding cable lug to the grounding points, first with the washers, then
7.
with the screws.
Verify that the grounding cabling is correct, that the grounding cable does not touch
8.
or block access to router components, and that it does not drape where people could
trip on it.

Figure 71: Connecting the Grounding Cable

MX2020 Router Grounding Specifications on page 380
Preventing Electrostatic Discharge Damage to an MX2020 Router on page 320
Connecting AC Power to a MX2020 Router with Three-Phase Delta AC Power
Distribution Modules on page 117
Connecting AC Power to a MX2020 Router with Three-Phase Wye AC Power Distribution
Modules on page 122
Connecting Power to a DC-Powered MX2020 Router with Power Distribution Modules
on page 131
CAUTION:
Do not mix AC and DC power modules within the same router.
You connect AC power to the router with three-phase delta AC PDMs by connecting the
AC power cord from an AC PDM to an AC power source.
To connect an AC power cord to an AC power source:
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist, and connect
1.
the strap to an approved site ESD grounding point. See the instructions for your site.
Switch off the dedicated customer site circuit breakers. Ensure that the voltage across
2.
the AC power source cable leads is 0 V and that there is no chance that the cable
leads might become active during installation.
Chapter 9: Grounding and Providing Power to the MX2020 Router
117