E3-01 (Motor 2 Control Mode) Dependent Parameters - YASKAWA A1000 Technical Manual

High performance vector control drive type: cimr-a series models: 200 v class: 0.55 to 110 kw, 400 v class: 0.55 to 630 kw
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

No.
Name
o1-03
Digital Operator Display Selection
o1-04
V/f Pattern Display Unit
<6> Default setting is determined by parameter o2-04, Drive Model Selection.
<14> Default setting value is dependent on the motor code set to parameter E5-01.
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<41> This default value is a calculated as a percentage of the maximum output frequency.
<55> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percent (0.0 to 100.0%) instead of in Hz.
<56> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percent (0.0 to 40.0%) instead of in Hz.
<57> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percent (-100.0 to 100.0%) instead of in Hz.
 E3-01 (Motor 2 Control Mode) Dependent Parameters
Table B.4 E3-01 (Motor 2 Control Mode) Dependent Parameters and Default Values
No.
Name
C3-21
Motor 2 Slip Compensation Gain
C3-22
Motor 2 Slip Compensation Primary Delay Time
C5-21
Motor 2 ASR Proportional Gain 1
C5-22
Motor 2 ASR Integral Time 1
C5-23
Motor 2 ASR Proportional Gain 2
C5-24
Motor 2 ASR Integral Time 2
C5-26
Motor 2 Carrier Frequency Selection
E3-04
Motor 2 Maximum Output Frequency
E3-05
Motor 2 Maximum Output Voltage
E3-06
Motor 2 Base Frequency
E3-07
Motor 2 Mid Output Frequency
E3-08
Motor 2 Mid Output Frequency Voltage
E3-09
Motor 2 Minimum Output Frequency
E3-10
Motor 2 Minimum Output Voltage
E3-04 to
The default setting of these parameters depends on the control mode but also on the drive capacity They are equivalent to the motor 1 settings. Refer to
E3-10
Values on page
522.
<9> Default setting is determined by the drive model (o2-04) and duty selection (C6-01).
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
B.4 Control Mode Dependent Parameter Default Values
Setting Range
0 to 3
0 to 1
Setting Range
0.0 to 2.5
0 to 10000
0.00 to 300.00
0.000 to 10.000
0.00 to 300.00
0.000 to 10.000
1 to F
40.0 to 400.0
0.0 to 255.0
<18>
0.0 to 400.0
0.0 to 400.0
0.0 to 255.0
<18>
0.0 to 400.0
0.0 to 255.0
<18>
Control Modes (A1-02)
Resolution
OLV/PM (5)
0
Resolution
V/f (0)
0.1
0.0
1 ms
2000
0.01
0.001 s
0.01
0.001 s
7
<9>
0.1 Hz
60.0
0.1 V
200.0
0.1 Hz
60.0
0.1 Hz
3.0
0.1 V
15.0
0.1 Hz
1.5
0.1 V
9.0
AOLV/PM (6)
CLV/PM (7)
1
1
1
1
Control Modes (E3-01)
V/f w/PG (1)
OLV (2)
CLV (3)
1.0
200
0.20
20.00
0.200
0.500
0.02
20.00
0.050
0.500
7
7
7
<9>
<9>
60.0
60.0
60.0
200.0
200.0
200.0
60.0
60.0
60.0
3.0
3.0
15.0
11.0
1.5
0.5
9.0
2.0
V/f Pattern Default
1.0
<9>
0.0
0.0
0.0
0.0
B
521