4 Faults and alarms
4.2 List of faults and alarms
F33950
Encoder 3: Internal software error
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
VECTOR_G
Component:
Sensor Module Encoder 3
Reaction:
OFF1 (OFF2)
Acknowledge:
POWER ON
Cause:
An internal software error has occurred.
Fault value (r0949, interpret decimal):
Information about the fault source.
Only for internal Siemens troubleshooting.
Remedy:
- if necessary, upgrade the firmware in the Sensor Module to a later version.
- contact Technical Support.
A33999 (F, N)
Encoder 3: Unknown alarm
Message value:
New message: %1
Message class:
Actual position/speed value incorrect or not available (11)
Drive object:
VECTOR_G
Component:
Sensor Module Encoder 3
Reaction:
NONE
Acknowledge:
NONE
Cause:
A alarm has occurred on the Sensor Module for encoder 3 that cannot be interpreted by the Control Unit firmware.
This can occur if the firmware on this component is more recent than the firmware on the Control Unit.
Alarm value (r2124, interpret decimal):
Alarm number.
Note:
If required, the significance of this new alarm can be read about in a more recent description of the Control Unit.
Remedy:
- replace the firmware on the Sensor Module by an older firmware version (r0148).
- upgrade the firmware on the Control Unit (r0018).
Reaction upon F:
NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F34207 (N, A)
VSM: Temperature fault threshold exceeded
Message value:
%1
Message class:
Infeed faulted (13)
Drive object:
VECTOR_G
Component:
Voltage Sensing Module (VSM)
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The temperature (r3666) measured using the Voltage Sensing Module (VSM) has exceeded the threshold value
(p3668).
Note:
This fault can only be output if the temperature evaluation was activated (p3665 > 0).
Fault value (r0949, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
See also: r3666 (VSM temperature actual value), p3668 (VSM overtemperature shutdown threshold)
Remedy:
- check the fan.
- reduce the power.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
1852
Propagation:
LOCAL
Propagation:
LOCAL
Propagation:
LOCAL
List Manual (LH2), 07/2016, A5E03263479A