F34207 (N, A)
VSM: Temperature fault threshold exceeded
Message value:
%1
Message class:
Infeed faulted (13)
Drive object:
B_INF
Component:
Voltage Sensing Module (VSM)
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The temperature (r3666) measured using the Voltage Sensing Module (VSM) has exceeded the threshold value
(p3668).
Note:
This fault can only be output if the temperature evaluation was activated (p3665 > 0).
Fault value (r0949, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
See also: r3666 (VSM temperature actual value), p3668 (VSM overtemperature shutdown threshold)
Remedy:
- check the fan.
- reduce the power.
- check the temperature sensor type setting (p3665).
- infeed: check the line filter type setting (p0220).
See also: p3665 (VSM temperature evaluation sensor type)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A34211 (F, N)
VSM: Temperature alarm threshold exceeded
Message value:
%1
Message class:
Infeed faulted (13)
Drive object:
VECTOR_G
Component:
Voltage Sensing Module (VSM)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r3666) measured using the Voltage Sensing Module (VSM) has exceeded the threshold value
(p3667).
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
See also: r3666 (VSM temperature actual value), p3667 (VSM overtemperature alarm threshold)
Remedy:
- check the fan.
- reduce the power.
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A34211 (F, N)
VSM: Temperature alarm threshold exceeded
Message value:
%1
Message class:
Infeed faulted (13)
Drive object:
B_INF
Component:
Voltage Sensing Module (VSM)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r3666) measured using the Voltage Sensing Module (VSM) has exceeded the threshold value
(p3667).
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
See also: r3666 (VSM temperature actual value), p3667 (VSM overtemperature alarm threshold)
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
LOCAL
Propagation:
LOCAL
Propagation:
LOCAL