Setting item
External command
[Pr.42]
function selection
: Set the external command signal (DI) in " [Pr.95] External command signal selection" at QD77MS16 use.
Refer to Chapter 5 "Data Used for Positioning Control" for details on the setting details.
Setting item
[Cd.3]
Positioning start No.
[Cd.8]
External command valid

[2] Starting by inputting external command signal

When starting positioning control by inputting the external command signal, the
start command can be directly input into the Simple Motion module. This allows
the variation time equivalent to one scan time of the PLC CPU to be eliminated.
This is an effective procedure when operation is to be started as quickly as
possible with the start command or when the starting variation time is to be
suppressed. To start positioning control by inputting the external command signal,
set the "data required to be set" and then turn ON the external command signal.

Restrictions

When starting by inputting the external command signal, the start complete signal
will not turn ON.

Data required to be set

Set the following data in advance.
Setting
value
0
Set to "0: External positioning start".
Set "[Cd.3] Positioning start No." and enable "[Cd.8] External command valid" with
a program. Then, turn ON the external command signal (DI).
Setting
value
1 to
Set the positioning data No. to be started.
600
1
Set to "1: Validates an external command.".
Chapter 6 Sequence Program Used for Positioning Control
Setting details
Setting details
6 - 66
Buffer memory address
62+150n
n: Axis No.-1
Buffer memory address
QD77MS2
QD77MS16
QD77MS4
1500+100n
4300+100n
1505+100n
4305+100n
n: Axis No.-1