[5] Setting the skip function using an external command signal

The skip function can also be executed using an "external command signal".
The following shows the settings and sequence program example for skipping
the control being executed in axis 1 using an "external command signal".
(1) Set the following data to execute the skip function using an external
Setting item
External
command function
[Pr.42]
selection
External
[Pr.95]
command signal
selection
External
[Cd.8]
command valid
: Refer to Section 5.2 "List of parameter" or Section 5.7 "List of control data" for details on the setting details.
(2) Add the following sequence program to the control program, and write it to
[QD77MS4 program example]
Skip function
selection command
command signal.
(The setting is carried out using the sequence program shown below in
section (2)).
Setting
value
3
Set "3: Skip request".
1
Set "1: DI1".
1
Set "1: Validate external command".
the PLC CPU.
Input external command signal
13 - 75
Chapter 13 Control Sub Functions
Setting details
TOP
H0
K62
K3
K1
Skip request
TOP
H0
K1505
K1
K1
External command valid
Buffer memory address
QD77MS2
QD77MS16
QD77MS4
62+150n
69+150n
1505+100n 4305+100n
n: Axis No.-1
<Select skip request>
<Set external command valid>