External I/O Signal Connection Example Using An External Safety Relay Unit - Mitsubishi Electric MELSERVO MR-J5 Series User Manual

Ac servo system
Hide thumbs Also See for MELSERVO MR-J5 Series:
Table of Contents

Advertisement

External I/O signal connection example using an external safety
relay unit
This connection is for source interfaces. For the other I/O signals, refer to the following connection examples.
Page 53 MR-J5-_G_ (excluding MR-J5-_G_-HS_)
Page 59 MR-J5W_-_G_
Page 62 MR-J5-_B_
Page 65 MR-J5W_-_B_
Page 68 MR-J5-_A_
This connection example complies with the requirements up to ISO/EN ISO 13849-1:2015 Category 3 PL e and IEC/EN IEC
62061 maximum SIL 3.
For details, refer to the safety relay module user's manual.
The safety level depends on the setting values of [Pr. PF18 STO diagnosis error detection time] and [Pr. PSD18_Permissible
time for mismatches DI1] and whether STO input diagnosis by TOFB output is performed or not.
24 V
Fuse
+24V
Safety relay
module
Power
MELSEC
supply
(QS90SR2S)
24G
S1 or
EMG
0 V
S1: STO shut-off switch (STO switch)
S2: Start switch (STO release switch)
S3: ON switch S4: OFF switch
KM1: Magnetic contactor
K3: Safety relay EMG:
Emergency stop switch
8 USING STO FUNCTION
456
8.3 Connection example
S2
K3
XS0
XS1
Z00 Z10 Z20
Control
circuit
X0
Z01 Z11 Z21
X1
COM0
COM1
*1
S4
S3
KM1
KM1
Servo amplifier
CN8
Control circuit
STO1
STO2
STOCOM
TOFB1
K3
TOFB2
TOFCOM
CN3
EMG
KM1
EM1
or
EM2
M
Servo motor