[7] Setting when the control unit is "degree"

Current value address

The "[Md.20] Current feed value" address is a ring address between 0 and
359.99999 ° .
Fig. 13.15 Current value address when the control unit is "degree".

Setting the software stroke limit

The upper limit value/lower limit value of the software stroke limit is a value
between 0 and 359.99999 ° .
(1) Setting when the software stroke limit is to be validated.
When the software stroke limit is to be validated, set the upper limit value in a
clockwise direction from the lower limit value.
Lower limit
315
(a) Set the movement range of section A as follows.
Software stroke limit lower limit value ................ 315.00000
Software stroke limit upper limit value ................ 90.00000
(b) Set the movement range of section B as follows.
Software stroke limit lower limit value ................ 90.00000
Software stroke limit upper limit value ................ 315.00000
Fig. 13.16 Software stroke limit when the control unit is "degree"
359.99999°
359.99999°
Set in a clockwise direction
Section A
Upper limit
90
Section B
13 - 34