Specifications Of Recommended Manual Pulse Generator - Mitsubishi Electric QD77MS User Manual

Hide thumbs Also See for QD77MS:
Table of Contents

Advertisement

[External input wiring connector]
Part name
Applicable connector
Applicable wire size

Specifications of recommended manual pulse generator

Item
Model name
Ambient temperature
Pulse resolution
Output method
Power supply voltage
Current consumption
Output level
Life time
Permitted axial loads
Weight
Number of max. revolution
Pulse signal status
Start friction torque
(Note-1): If a separate power supply is used, use a stabilized power supply of voltage 5VDC ± 0.25V.
A6CON1, A6CON2, A6CON3, A6CON4 (Sold separately)
2
0.3mm
(When A6CON1 and A6CON4 are used), AWG28 to AWG24 (When A6CON2 is used),
AWG28 (twisted)/AWG30 (single wire) (When A6CON3 is used)
25PLS/rev (100 PLS/rev after magnification by 4)
Voltage-output, Output current Max. 20mA
"H" level : Power supply voltage
"L" level : 0.5V or less (with maximum leading-in)
Instantaneous Max. 600r/min. normal 200r/min
2 signals: A phase, B phase, 90° phase difference
Specification
Specification
MR-HDP01
-10 to 60°C (14 to 140°F )
4.5 to 13.2VDC
60mA
(Note-1)
1000000 revolutions (at 200r/min)
Radial load: Max. 19.6N
Thrust load: Max. 9.8N
0.4 [kg]
0.06N•m (20°C (68°F))
2 - 5
Chapter 2 System Configuration
-1V or more (in no load)