Operation When A Skip Signal Is Input During Positioning Control - Mitsubishi Electric QD77MS User Manual

Hide thumbs Also See for QD77MS:
Table of Contents

Advertisement

[2] Control details
[QD77MS4 operation example]
Positioning start signal
[Y10, Y11, Y12, Y13]
BUSY signal
[XC, XD, XE, XF]
Positioning complete signal
[X14, X15, X16, X17]
Positioning
Skip signal
Fig. 13.37 Operation when a skip signal is input during positioning control
[3] Precautions during control
The following drawing shows the skip function operation.
ON
OFF
ON
OFF
OFF
V
Deceleration by
skip signal
OFF
(1) If the skip signal is turned ON at the last of an operation, a deceleration stop
will occur and the operation will be terminated.
(2) When a control is skipped (when the skip signal is turned ON during a
control), the positioning complete signals will not turn ON.
(3) When the skip signal is turned ON during the dwell time, the remaining dwell
time will be ignored, and the next positioning data will be executed.
(4) When a control is skipped during interpolation control, the reference axis
skip signal is turned ON. When the reference axis skip signal is turned ON,
a deceleration stop will be carried out for every axis, and the next reference
axis positioning data will be executed.
(5) The M code ON signals will not turn ON when the M code output is set to
the AFTER mode (when "1: AFTER mode" is set in "[Pr.18] M code ON
signal output timing").
(In this case, the M code will not be stored in "[Md.25] Valid M code".)
(6) The skip cannot be carried out by the speed control and position-speed
switching control.
(7) If the skip signal is turned ON with the M code signal turned ON, the
transition to the next data is not carried out until the M code signal is turned
OFF.
Start of the
next positioning
ON
(Note): Refer to Section 3.3 for input/output signal of QD77MS16.
13 - 73
Chapter 13 Control Sub Functions
ON
t

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents