Wiring The Forced Stop; Operation For The Forced Stop Function; Wiring When Using The Forced Stop - Mitsubishi Electric QD77MS User Manual

Hide thumbs Also See for QD77MS:
Table of Contents

Advertisement

[QD77MS4 operation example]
Each operation
PLC READY signal[Y0]
All axis servo ON[Y1]
Positioning start signal[Y10]
Forced stop input
(Input voltage of EMI)
Md.50
Forced stop input
Md.108
Servo status
(b1: Servo ON)
Pr.82
Forced stop valid/
invalid selection
The following drawing shows the operation of the forced stop function.
1
ON
(Note): Refer to Section 3.3 for input/output signal and Chapter 5 for buffer memory address of QD77MS16.
Fig. 13.18 Operation for the forced stop function

[2] Wiring the forced stop

When using the forced stop function, wire the terminals of the Simple Motion
module forced stop input as shown in the following drawing. As for the 24VDC
power supply, the direction of current can be switched.
Simple Motion module
Fig. 13.19 Wiring when using the forced stop
Forced stop
causes occurrence
0
OFF
0
Forced stop valid
EMI
24VDC
EMI.COM
13 - 40
Chapter 13 Control Sub Functions
Forced stop
causes occurrence
1
0
ON
OFF
1
ON

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents