F07450 (A)
LR: Standstill monitoring has responded
Message value:
-
Message class:
Application / technological function faulted (17)
Drive object:
VECTOR_G
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
After the standstill monitoring time (p2543) expired, the drive left the standstill window (p2542).
- position actual value inversion incorrectly set (p0410).
- standstill window set too small (p2542).
- standstill monitoring time set too low (p2543).
- position loop gain too low (p2538).
- position loop gain too high (instability/oscillation, p2538).
- mechanical overload.
- Connecting cable, motor/drive converter incorrect (phase missing, interchanged).
- when selecting motor identification, select tracking mode (BI: p2655[0] = 1 signal).
- when selecting function generator, select tracking mode (BI: p2655[0] = 1 signal) and de-activate position control
(BI:p2550 = 0 signal).
Remedy:
Check the causes and resolve.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F07451 (A)
LR: Position monitoring has responded
Message value:
-
Message class:
Application / technological function faulted (17)
Drive object:
VECTOR_G
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
When the position monitoring time (p2545) expired, the drive had still not reached the positioning window (p2544).
- positioning window parameterized too small (p2544).
- position monitoring time parameterized too short (p2545).
- position loop gain too low (p2538).
- position loop gain too high (instability/oscillation, p2538).
- drive mechanically locked.
Remedy:
Check the causes and resolve.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F07452 (A)
LR: Following error too high
Message value:
-
Message class:
Application / technological function faulted (17)
Drive object:
VECTOR_G
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The difference between the position setpoint position actual value (following error dynamic model, r2563) is higher
than the tolerance (p2546).
- the drive torque or accelerating capacity exceeded.
- position measuring system fault.
- position control sense incorrect.
- mechanical system locked.
- excessively high traversing velocity or excessively high position reference value (setpoint) differences
Remedy:
Check the causes and resolve.
Reaction upon A:
NONE
Acknowl. upon A:
NONE