Siemens SINAMICS G150 Manual page 1394

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

4 Faults and alarms
4.2 List of faults and alarms
Alarm value (r2124, interpret binary):
Bit 0 = 1: Publisher with address in r2077[0], connection failed.
...
Bit 15 = 1: Publisher with address in r2077[15], connection failed.
Remedy:
- check the PROFIBUS cables.
- carry out a first commissioning of the Publisher that has the failed connection.
See also: r2077 (PROFIBUS diagnostics peer-to-peer data transfer addresses)
F01946 (A)
PROFIBUS: Connection to the Publisher aborted
Message value:
Fault cause: %1 bin
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Reaction:
Vector: OFF1 (NONE, OFF2, OFF3)
Infeed: OFF1 (NONE, OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
At this drive object, the connection to at least one Publisher for PROFIBUS peer-to-peer data transfer in cyclic
operation has been aborted.
Fault value (r0949, interpret binary):
Bit 0 = 1: Publisher with address in r2077[0], connection aborted.
...
Bit 15 = 1: Publisher with address in r2077[15], connection aborted.
Remedy:
- check the PROFIBUS cables.
- check the state of the Publisher that has the aborted connection.
See also: r2077 (PROFIBUS diagnostics peer-to-peer data transfer addresses)
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F01950 (N, A)
PB/PN clock cycle synchronous operation synchronization unsuccessful
Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Reaction:
OFF1 (NONE)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Synchronization of the internal clock cycle to the global control telegram has failed. The internal clock cycle exhibits
an unexpected shift.
Remedy:
Only for internal Siemens troubleshooting.
Note:
PB: PROFIBUS
PN: PROFINET
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F01951
CU SYNC: Synchronization application clock cycle missing
Message value:
%1
Message class:
Internal (DRIVE-CLiQ) communication error (12)
Drive object:
All objects
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
If DRIVE-CLiQ components with different application clock cycle are operated on a DRIVE-CLiQ port, this requires
synchronization with the Control Unit. This synchronization routine was unsuccessful.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
1394
SINAMICS G130/G150