4 Faults and alarms
4.2 List of faults and alarms
For communication with PROFIsafe F-Host, the following applies:
- Check any other PROFIsafe communication messages/signals present and evaluate them.
- check the operating state of the F-Host.
- Check the communication connection to the F Host.
- Check the communication connection to the Motor Module/Hydraulic Module. It must be ensured that when the
Control Unit powers up, the Motor Module/Hydraulic Module is connected and at the latest is also switched-on with
the Control Unit. Otherwise, if the Motor Module/Hydraulic Module is subsequently inserted or switched-on, a
POWER ON must be performed at the Control Unit.
See also: p9601 (SI enable functions integrated in the drive (Control Unit)), p9801 (SI enable functions integrated in
the drive (Motor Module)), p10010 (SI TM54F drive object assignment)
Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
Reaction upon N:
NONE
Acknowl. upon N:
NONE
C01797
SI Motion P1 (CU): Axis not safely referenced
Message value:
%1
Message class:
Safety monitoring channel has identified an error (10)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The standstill position saved before powering down does not match the actual position determined at power-up.
Message value (r9749, interpret decimal):
1: Axis not safely referenced.
2: User agreement missing.
Remedy:
If safe automatic referencing is not possible the user must issue a user agreement for the new position using the
softkey. This mean that this position is then designated as safety-relevant.
Note:
SI: Safety Integrated
C01798
SI Motion P1 (CU): Test stop running
Message value:
-
Message class:
Safety monitoring channel has identified an error (10)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The test stop is active.
Remedy:
Not necessary.
The message is withdrawn when the test stop is finished.
Note:
SI: Safety Integrated
C01799
SI Motion P1 (CU): Acceptance test mode active
Message value:
-
Message class:
Safety monitoring channel has identified an error (10)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The acceptance test mode is active.
This means the following:
- the setpoint velocity limiting is deactivated (r9733).
- the standard limit switches are deactivated during the acceptance test for function SLP (SE) (for EPOS internal,
otherwise via r10234).
- for safety functions with SINUMERIK, the following applies: The POWER ON signals of the safety-relevant motion
monitoring functions can be acknowledged during the acceptance test using the acknowledgement functions of the
higher-level control.
1386
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A