This is the reason that when booting, an attempt is made to copy SI parameters from monitoring channel 1 to
monitoring channel 2. However, no safety-relevant function has been selected on monitoring channel 1 (p9501 = 0,
p9601 = 0). Copying was rejected for safety reasons.
As a consequence, inconsistent parameterization can occur in both monitoring channels, which in turn results in
additional error messages.
Especially for inconsistent enabling of the safety functions on both monitoring channels (p9601 = 0, p9801 <> 0), fault
F30625 is output.
Note:
This fault does not result in a safety stop response.
See also: p9700 (SI Motion copy function)
Remedy:
- Set p9700 to 0.
- Check p9501 and p9601 and if required, correct.
- Restart the copying function by entering the corresponding value into p9700.
Alternatively, using the STARTER commissioning tool, perform the following steps in the online mode:
- Call the "Safety Integrated" screen form (the field "Select safety functions" is at "No Safety Integrated").
- Click on "Change settings".
- Click on "Activate settings" (as a consequence, Safety Integrated is inhibited on both monitoring channels).
- save all parameters (p0977 = 1 or "copy RAM to ROM").
- carry out a POWER ON (power off/on) for all components.
F01664
SI P1 (CU): No automatic firmware update
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
During booting, the system detected that the "Firmware update automatic" function (p7826 = 1) was not activated.
This function must be activated for automatic firmware updates/downgrades to prevent impermissible version
combinations when safety functions are enabled.
Note:
This fault does not result in a safety stop response.
See also: p7826 (Firmware update automatic)
Remedy:
When safety functions are enabled (p9501 <> 0 and/or p9601 <> 0):
1. Activate the "Firmware update automatic" function (p7826 = 1).
2. Save the parameters (p0977 = 1) and carry out a POWER ON.
When de-activating the safety functions (p9501 = 0, p9601 = 0), the fault can be acknowledged after exiting the
safety commissioning mode.
F01665
SI P1 (CU): System is defective
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
VECTOR_G
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A system defect was detected before the last boot or in the actual one. The system might have been rebooted
(reset).
Fault value (r0949, interpret hexadecimal):
200000 hex, 400000 hex, 8000yy hex (yy any):
- Fault in the actual booting/operation.
800004 hex:
- Parameters p9500/p9300 are, under certain circumstances, not the same. In addition, Safety message
C01711/C30711 is displayed.
Additional values:
- defect before the last time that the system booted.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1349