A05006 (N)
Power unit: Overtemperature thermal model
Message value:
-
Message class:
Power electronics faulted (5)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature difference between the chip and heat sink has exceeded the permissible limit value (blocksize
power units only).
Depending on p0290, an appropriate overload response is initiated.
See also: r0037
Remedy:
Not necessary.
The alarm disappears automatically once the limit value is undershot.
Note:
If the alarm does not disappear automatically and the temperature continues to rise, this can result in fault F30024.
See also: p0290 (Power unit overload response)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
N05007 (A)
Power unit: Overtemperature thermal model (chassis PU)
Message value:
-
Message class:
Power electronics faulted (5)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature difference between the chip and heat sink has exceeded the permissible limit value (r0293) (chassis
power units only).
Depending on p0290, an appropriate overload response is initiated.
See also: r0037, r0293 (Power unit alarm threshold model temperature)
Remedy:
Not necessary.
The alarm disappears automatically once the limit value is undershot.
See also: p0290 (Power unit overload response)
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F05050
Parallel circuit: Pulse enable in spite of pulse inhibit
Message value:
%1
Message class:
Application / technological function faulted (17)
Drive object:
B_INF, VECTOR_G
Reaction:
Vector: OFF2 (NONE, OFF1, OFF3, STOP2)
Infeed: OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
A power unit signals that the pulses are enabled although the pulses are inhibited.
Fault value (r0949, interpret decimal):
Number of the power unit involved.
Remedy:
The power unit is defective and must be replaced.
F05051
Parallel circuit: Power unit pulse enable missing
Message value:
%1
Message class:
Application / technological function faulted (17)
Drive object:
B_INF, VECTOR_G
Reaction:
Vector: OFF2 (NONE, OFF1, OFF3, STOP2)
Infeed: OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
For one or several power units, the pulses were not able to be enabled.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1417