4 Faults and alarms
4.2 List of faults and alarms
Remedy:
Use power units with the same firmware version.
For parallel circuit configurations, only power units with identical firmware versions may be used.
F05058
Parallel circuit: VSM EEPROM versions differ
Message value:
Parameter: %1
Message class:
General drive fault (19)
Drive object:
B_INF, VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The EEPROM versions of the Voltage Sensing Modules (VSM) do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy:
For parallel circuit configurations, only Voltage Sensing Modules (VSM) with identical EEPROM versions may be
used.
F05059
Parallel circuit: VSM firmware versions differ
Message value:
Parameter: %1
Message class:
General drive fault (19)
Drive object:
B_INF, VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The firmware versions of the Voltage Sensing Module (VSM) do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy:
For parallel circuit configurations, only Voltage Sensing Modules (VSM) with identical firmware versions may be
used.
F05060
Parallel circuit: Power unit firmware version does not match
Message value:
Parameter: %1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, VECTOR_G
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
Firmware from version V02.30.01.00 is required when connecting the power units in parallel.
Remedy:
Update the firmware of the power units (at least V02.30.01.00).
F05061
Infeed VSM count
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The number of active Voltage Sensing Modules (VSM) for the drive object infeed with chassis power units is not
correct.
For A_Infeed, each active power unit must be assigned an active VSM also for a parallel circuit configuration.
For S_Infeed, the active drive object, must be assigned at least one active VSM.
Fault value (r0949, interpret decimal):
Number of VSMs that are currently assigned to the drive object.
Remedy:
Adapts the number of active Voltage Sensing Modules (VSM).
1420
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A