Siemens SINAMICS G150 Manual page 1457

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

F07485 (A)
EPOS: Fixed stop not reached
Message value:
-
Message class:
Application / technological function faulted (17)
Drive object:
VECTOR_G
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
In a traversing block with the task FIXED STOP, the end position was reached without detecting a fixed stop.
Remedy:
- check the traversing block and locate the target position further into the workpiece.
- check the "fixed stop reached" control signal (p2637).
- if required, reduce the maximum following error window to detect the fixed stop (p2634).
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A07486
EPOS: Intermediate stop missing
Message value:
-
Message class:
Application / technological function faulted (17)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
In the modes "traversing blocks" or "direct setpoint input/MDI" at the start of motion, the binector input "no
intermediate stop/intermediate stop" (BI: p2640) did not have a 1 signal.
Remedy:
Connect a 1 signal to the binector input "no intermediate stop/intermediate stop" (BI: p2640) and re-start motion.
A07487
EPOS: Reject traversing task missing
Message value:
-
Message class:
Application / technological function faulted (17)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
In the modes "traversing blocks" or "direct setpoint input/MDI" at the start of motion, the binector input "do not reject
traversing task/reject traversing task" (BI: p2641) does not have a 1 signal.
Remedy:
Connect a 1 signal to the binector input "do not reject traversing task/reject traversing task" (BI: p2641) and restart
motion.
F07488
EPOS: Relative positioning not possible
Message value:
-
Message class:
Application / technological function faulted (17)
Drive object:
VECTOR_G
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
In the mode "direct setpoint input/MDI", for continuous transfer (p2649 = 1) relative positioning was selected (BI:
p2648 = 0 signal).
Remedy:
Check the control.
A07489
EPOS: Reference point correction outside the window
Message value:
-
Message class:
Application / technological function faulted (17)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
For the function "flying referencing" the difference between the measured position at the measuring probe and the
reference point coordinate lies outside the parameterized window.
Remedy:
- check the mechanical system.
- check the parameterization of the window (p2602).
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1457