CPU Unit Operating Modes
Duplex Refreshing
9-2
CPU Unit Operating Modes
9-2-1
Operating Modes
9-2-2
Status and Operations in Each Operating Mode
Overall Operation
Mode
Program
(See note)
PROGRAM
Stopped
RUN
Executed
MONITOR
Executed
Programming Console Operations
Mode
Monitor I/O
Memory
PROGRAM
OK
MONITOR
OK
RUN
OK
350
Duplex operating status does not exist during duplex initialization (i.e., duplex
initialization is performed in simplex operating status). This means that the
active CPU Unit will not be switched. Because of this, operation will not con-
tinue if an error that would cause the CPU Unit to be switched occurs during
duplex initialization, including CPU errors, memory errors, fatal Inner Board
errors, program errors, exceeding the cycle time limit, and execution of FALS
instructions).
Duplex refreshing is used to transfer errors detected by the active CPU Unit or
the status of special flags and bits changed by the active CPU Unit to the
standby CPU Unit. It is performed only in Duplex Mode.
The CPU Unit has three operating modes that control the entire user program
and are common to all tasks.
PROGRAM:
Programs are not executed and preparations, such as creat-
ing I/O tables, initializing the PLC Setup and other settings,
transferring programs, checking programs, force-setting and
force-resetting can be executed prior to program execution.
MONITOR:
Programs are executed, but some operations, such as online
editing, forced-set/reset, and changes to present values in I/
O memory, are enabled for trial operation and other adjust-
ments.
RUN:
Programs are executed and some operations are disabled.
PROGRAM, RUN, and MONITOR are the three operating modes available in
the CPU Unit. The following lists status and operations for each mode.
I/O refresh
External outputs
Executed
OFF
Executed
Controlled by pro-
gram
Executed
Controlled by pro-
gram
Monitor
Transfer Program
Program
PLC to
Programming
Device
OK
OK
OK
OK
OK
OK
I/O Memory
Non-holding
areas
Clear
Controlled by program
Controlled by program
Check
Program
Programming
Device to PLC
OK
OK
X
X
X
X
Section 9-2
Holding areas
Hold
Create I/O
Table
OK
X
X