Duplex Unit
54
by peripheral bus to a baud rate other than those that are automatically de-
tected, the auto-detection function will not work.
2. The order of automatic detection is as follows: 9,600 bps, 19,200 bps,
38,400 bps, and then 115,200 bps. If the Programming Device is in a mode
other than peripheral bus, or if it is set by peripheral bus to a baud rate oth-
er than those that are automatically detected, the auto-detection function
will not work.
3. For details on the PLC Setup, refer to SECTION 6 PLC Setup.
4. When connecting a CX-Programmer to the peripheral port or RS-232C
port, set the CX-Programmer's network classification and either the
PRPHL pin or the COMM pin on the DIP switch as shown in the following
table.
CX-Programmer's
network setting
Peripheral bus
SYSWAY (Host Link) Set the PRPHL
5. Be sure to set the RSV (reserve) pin to OFF.
Connecting to
Connecting to
peripheral port
RS-232C port
Set the PRPHL
Set the COMM pin
pin to OFF.
to ON.
Set the COMM pin
pin to ON.
to OFF.
Section 2-3
PLC Setup
---
Set to "Host Link."