Omron SYSMAC CS1D-PD Series Operation Manual page 74

Duplex system

Advertisement

Specifications
Item
CS1D Power Supply Unit
RUN output
Contact configu-
(See note 3.)
ration
Switch capacity
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Ambient operating temperature
Ambient operating humidity
Atmosphere
Ambient storage temperature
Grounding
Enclosure
Weight
CPU Rack dimensions
Expansion Rack dimensions
Safety standards
Note
34
CS1D-PA207R
SPST-NO
240 V AC, 2A (resistive
load)
120 V AC, 0.5 A (induction
load)
24 V DC, 2A (resistive
load)
24 V DC, 2 A (induction
load)
20 MΩ min. (at 500 V DC)
between AC external and
GR terminals (See note 2.)
2,300 V AC 50/60 Hz for 1
min between AC external
and GR terminals (See
note 2.)
Leakage current: 10 mA
max.
1,000 V AC 50/60 Hz for 1
min between AC external
and GR terminals (See
note 2.)
Leakage current: 10 mA
max.
2 kV on power supply line (conforming to IEC61000-4-4)
10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s
directions for 80 minutes
(Time coefficient: 8 minutes × coefficient factor 10 = total time 80 min.)
2
147 m/s
3 times each in X, Y, and Z directions (according to JIS 0041)
0 to 55°C
10% to 90% (with no condensation)
Must be free from corrosive gases.
−20 to 75°C (excluding battery)
Less than 100 Ω
Mounted in a panel.
Refer to SECTION 2 Specifications, Nomenclature, and Functions.
5 slots (CS1D-BC052): 505 × 130 × 153 mm (W x H x D) (See note 4.)
9 slots (CS1D-BI092): 505 × 130 × 153 mm (W x H x D) (See note 4.)
Conforms to cULus, NK, Lloyd's, and EU Directives.
1. The above inrush current value is for a cold start at normal temperatures.
The inrush current circuit for this power supply includes a thermistor ele-
ment (for current suppression at low temperatures). If the ambient temper-
ature is too high, the thermistor element will not be cool enough, so the
above inrush current value may be exceeded (by as much as double the
value shown). Provide a sufficient margin by taking this into consideration
along with breaking or detection characteristics when selecting fuses and
breakers for external circuits.
2. Disconnect the CS1D Power Supply Unit's LG terminal from the GR termi-
nal when testing insulation and dielectric strength. Testing the insulation
and dielectric strength with the LG terminal and the GR terminals connect-
ed will damage internal circuits in the CPU Unit.
3. Supported when mounted to a Backplane.
Specifications
CS1D-PD024
Not provided.
20 MΩ min. (at 500 V DC)
between DC external and
GR terminals (See note 2.)
1,000 V AC 50/60 Hz for 1
min between DC external
and GR terminals (See note
2.)
Leakage current: 10 mA
max.
Section 2-1
CS1D-PD025
Not provided.
20 MΩ min. (at 500 V DC)
between DC external and
GR terminals (See note 2.)
1,000 V AC 50/60 Hz for 1
min between DC external
and GR terminals (See note
2.)
Leakage current: 10 mA
max.
2
in X, Y, and Z