PLC Setup Coding Sheets for Programming Console
84@@@@
Value (hex)
A
8000
Don't wait.
0000
Wait for all Boards.
95@@@@
Value (hex)
A
0000
Not duplex for unit numbers 0 to 15. Bits 00 to 14 correspond
0001
Unit number 0 set as primary Unit.
to
4000
Unit number 14 set as primary Unit.
Note The unit number of the secondary Unit is one higher than that of the pri-
mary Unit.
96@@@@
Value (hex)
A
0000
Transfer program
8000
Don't transfer program
40@@
Transfer program
C0@@
Don't transfer program
Note The above settings assume that both bit 11 (Inner Board parameter
area) and bit 10 (Inner Board variable area) are set to 0.
121@@@@
Value (hex)
A
0000
Not duplex for unit numbers 0 to 15.
0001
Duplex for only unit number 0.
to
8000
Duplex for only unit number 15.
Note Up to three bits may be turned ON at the same time.
122@@@@
Value (hex)
A
0000
Allow only one Unit to be replaced online at a time.
8000
Allow simultaneous online replacement of more than one Unit.
A
Inner Board Setting
A
Primary/Secondary Duplex Communications Unit
Settings
(Duplex CPU Systems only)
A
Duplex Transfer Settings
Program transfer
A
Duplex Communications Unit Settings
A
Multiple Unit Online Replacement
Appendix D
to unit numbers 0 to 14.
EM Area transfer
Transfer together
Transfer together
Transfer over multiple scans
Transfer over multiple scans
Bits 00 to 15 corre-
spond to unit num-
bers 0 to 15.
583