Table 150: Register Address 0x1029

Register Address 0x1029 (4137
Value
Access
Description

Table 151: Register Address 0x102A

Register address 0x102A (4138
Value
Access
Description

Table 152: Register Address 0x102B

Register Address 0x102B (4139
Value
Access
Description

Table 153: Register Address 0x1030

Register address 0x1030 (4144
Value
Access
Default
Description

Table 154: Register Address 0x1031

Register address 0x1031 (4145
Value
Access
Description
Manual
1.5.0
750-882 Media Redundancy ETHERNET Controller
) with 9 Words
dec
MODBUS TCP statistics
Read/write
1 word SlaveDeviceFailure
1 word BadProtocol
1 word BadLength
1 word BadFunction
1 word BadAddress
1 word BadData
1 word TooManyRegisters
1 word TooManyBits
1 word ModTcpMessageCounter  Number of received MODBUS/TCP
By writing 0xAA55 or 0x55AA the register is reset.
) with a word count of 1
dec
MODBUS/TCP connections
Read
Number of TCP connections
) with a Word Count of up to 1
dez
Local bus reset
Write
Writing of this register restarts the local bus
) with a word count of 1
dec
Configuration MODBUS/TCP time-out
Read/write
0x0258 (600 decimal)
This is the maximum number of milliseconds the fieldbus coupler will allow a
MODBUS/TCP connection to stay open without receiving a MODBUS request.
Upon time-out, idle connection will be closed. Outputs remain in last state.
Default value is 600 ms (60 seconds), the time base is 100 ms, the minimal value
is 100 ms. If the value is set to '0', the timeout is disabled. On this connection, the
watchdog is triggered with a request.
) with a word count of 3
dec
Read the MAC-ID of the controller
Read
This register gives the MAC-ID, with a length of 3 words
WAGO-I/O-SYSTEM 750
 local bus error, fieldbus error by activated
watchdog
 error in the MODBUS TCP header
 Wrong telegram length
 Invalid function code
 Invalid register address
 Invalid value
 Number of the registers which can be
worked on is too large, Read/Write 125/100
 Number of the coils which can be worked on
is too large, Read/Write 2000/800
requests