84
Function Description
7.2.3
Example of an Output Data Process Image
The following example for the output process image comprises 2 digital and 4
analog outputs. It comprises 4 words for the analog outputs and 1 word for the
digital outputs; i.e., 5 words in total.
In addition, the output data can also be read back with an offset of 200
(0x0200) added to the MODBUS address.
Data > 256 words can be read back by using the cumulative offset!
All output data greater than 256 words and, therefore located in the memory
range 6000
1000
(0x1000) added to the MODBUS address.
hex
Figure 40: Example of Process Image for Output Data
Manual
1.5.0
750-882 Media Redundancy ETHERNET Controller
(0x6000) to 66F9
hex
hex
WAGO-I/O-SYSTEM 750
(0x66F9) can be read back with an offset of
hex