Snmp - WAGO -I/O-SYSTEM 750 Manual

Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 Configuring via the Web-Based Management System (WBM) 165
750-882 Media Redundancy ETHERNET Controller
10.6

SNMP

On the WBM page "SNMP", you can perform the settings for the Simple Network
Management Protocol.
SNMP is a standard for device management within a TCP/IP network. The
Simple Network Management Protocol (SNMP) is responsible for transporting the
control data that allows the exchange of management information, the status and
statistic data between individual network components and a management
system.
The fieldbus controller supports SNMP in versions 1, 2c and 3.
The SNMP of the ETHERNET TCP/IP controller includes the general MIB
according to RFC1213 (MIB II).
SNMP is processed via port 161. The port number for SNMP traps (agent
messages) is 162.
Enable port 161 and 162 to use SNMP!
Enable ports 161 and 162 in the WBM in menu "port", so that the fieldbus
coupler/controller can be reached via SNMP. The port numbers cannot be
modified.
Modify parameter via WBM or SNMP objects!
However, parameters that can be set on the html pages can also be changed
directly by the appropriate SNMP objects.
Additional Information:
Additional information for SNMP, the Management Information Base (MIB) and
traps (event messages via SNMP) may be obtained from section "Fieldbus
Communication" > ... > "SNMP (Simple Network Management Protocol)."
Note that the settings for SNMPV1/V2c and SNMPV3 are separate from each
other: The different SNMP versions can be activated or used in parallel or
individually on a fieldbus controller.