13.2.5.17 Vibration Velocity/Bearing Condition Monitoring Vib I/O; 13.2.5.18 Knx/Eib/Tp1 Module; Table 414: Vibration Velocity/Bearing Condition Monitoring Vib I/O 750-645 - WAGO -I/O-SYSTEM 750 Manual

Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

364 I/O Modules

13.2.5.17 Vibration Velocity/Bearing Condition Monitoring VIB I/O

750-645
The Vibration Velocity/Bearing Condition Monitoring VIB I/O has a total of 12
bytes of user data in both the Input and Output Process Image (8 bytes of
module data and 4 bytes of control/status). The following table illustrates the
Input and Output Process Image, which have 8 words mapped into each image.
Word alignment is applied.

Table 414: Vibration Velocity/Bearing Condition Monitoring VIB I/O 750-645

Input and Output Process Image
Offset
0
1
2
3
4
5
6
7

13.2.5.18 KNX/EIB/TP1 Module

753-646
The KNX/TP1 module appears in router and device mode with a total of 24-byte
user data within the input and output area of the process image, 20 data bytes
and 2 control/status bytes. Even though the additional bytes S1 or C1 are
transferred as data bytes, they are used as extended status and control bytes.
The opcode is used for the read/write command of data and the triggering of
specific functions of the KNX/EIB/TP1 module. Word-alignment is used to assign
12 words in the process image. Access to the process image is not possible in
router mode. Telegrams can only be tunneled.
In device mode, access to the KNX data can only be performed via special
function blocks of the IEC application. Configuration using the ETS engineering
tool software is required for KNX.
Manual
1.5.0
750-882 Media Redundancy ETHERNET Controller
Byte Destination
High Byte
Low Byte
-
D1
-
D3
-
D5
-
D7
C0/S0
not used
D0
(log. Channel 1, Sensor input 1)
C1/S1
not used
D2
(log. Channel 2, Sensor input 2)
C2/S2
not used
D4
(log. Channel 3, Sensor input 3)
C3/S3
not used
D6
(log. Channel 4, Sensor input 2)
WAGO-I/O-SYSTEM 750
Description
Control/status byte
(log. Channel 1,
Sensor input 1)
Data bytes
Control/status byte
(log. Channel 2,
Sensor input 2)
Data bytes
Control/status byte
(log. Channel 3,
Sensor input 1)
Data bytes
Control/status byte
(log. Channel 4,
Sensor input 2)
Data bytes

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-882

Table of Contents