Table 64: Blink Code Table For The I/O Led Signaling, Error Code 6; Table 65: Blink Code Table For The I/O Led Signaling, Error Code 7; Table 66: Blink Code Table For The I/O Led Signaling, Error Code 8 - WAGO -I/O-SYSTEM 750 Manual

Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-882 Media Redundancy ETHERNET Controller

Table 64: Blink Code Table for the I/O LED Signaling, Error Code 6

Error code 6: "Fieldbus specific errors"
Error
Argument
1
2
3
4
5
6
7
8
9
10

Table 65: Blink Code Table for the I/O LED Signaling, Error Code 7

Error code 7: "Not supported I/O module"
Error
Argument
n

Table 66: Blink Code Table for the I/O LED Signaling, Error Code 8 ... 9

Error code 8 ... 9 –not used–
Error
Argument
-
Error description
Solution
1.
Invalid MACID
2.
3.
1.
Ethernet Hardware
initialization error
2.
1.
TCP/IP initialization
error
2.
Network configuration
1.
error (no IP Address)
1.
Application protocol
initialization error
2.
Process image is too
1.
large
2.
1.
Double IP address in
network
2.
1.
2.
Error when building the
3.
process image
4.
Error with mapping
between bus modules
1.
and fieldbus
Network configuration
1.
error (no IP Address on
port 2)
Error Description
Solution
1.
First unsupported
2.
I/O module
in place of n.
3.
Error Description
Solution
not used
Turn off the power supply of the node.
Exchange fieldbus controller.
Turn the power supply on again.
Restart the fieldbus controller by turning the power
supply off and on again.
If the error still exists, exchange the fieldbus controller.
Restart the fieldbus coupler by turning the power supply
off and on again.
If the error still exists, exchange the bus coupler.
Check the settings of BootP server.
Restart the fieldbus coupler by turning the power supply
off and on again.
If the error still exists, exchange the bus coupler.
Turn off the power supply of the node.
Reduce number of I/O modules
Change configuration. Use another IP address, which is
not yet present in network.
Restart the fieldbus coupler by turning the power supply
off and on again.
Turn off the power supply of the node.
Reduce number of I/O modules
Restart the fieldbus coupler by turning the power supply
off and on again.
If the error still exists, exchange the bus coupler.
Check EA-Config.xml file on the fieldbus controller
Check the settings of BootP server.
Turn off the power supply to the node.
Replace the nth I/O module containing process data or
reduce the number of modules to the number of n-1.
Turn the power supply on.
Diagnostics 203
-
Manual
1.5.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-882