Function Description
7.3.3
Data Exchange between MODBUS/TCP Master and I/O
Modules
Data exchange between the MODBUS/TCP Master and the I/O modules is
conducted using the MODBUS functions implemented in the controller by means
of bit-by-bit or word-by-word reading and writing routines.
There are 4 different types of process data in the controller:
Input words
Output words
Input bits
Output bits
Access by word to the digital I/O modules is carried out in accordance with the
following table:

Table 36: Allocation of Digital Inputs and Outputs to Process Data Words in Accordance with the

Intel Format
Digital inputs/
outputs
Process data
word
Byte
Output can be read back in by adding an offset of 200
MODBUS address.
Data > 256 words can be read back by using the cumulative offset!
All output data greater than 256 words and, therefore located in the memory
range 0x6000 to 0x62FC, can be read back by adding an offset of 1000
(0x1000) to the MODBUS address.
Manual
1.5.0
750-882 Media Redundancy ETHERNET Controller
16. 15. 14. 13. 12. 11. 10.
Bit
Bit
Bit
Bit
Bit
15
14
13
12
11
High byte D1
WAGO-I/O-SYSTEM 750
9.
8.
7.
Bit
Bit
Bit
Bit
Bit
Bit
10
9
8
7
6
(0x0200) to the
hex
6.
5.
4.
3.
2.
1.
Bit
Bit
Bit
Bit
Bit
5
4
3
2
1
Low byte D0
hex
0

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-882

Table of Contents