32
System Description
Fieldbus coupler or controller
Internal system supply module
Input current I
Activate all outputs when testing the current consumption!
If the electrical consumption of a power supply point for the 24 V system
supply exceeds 500 mA, then the cause may be an improperly
dimensioned node or a defect.
During the test, you must activate all outputs.
Manual
1.5.0
750-882 Media Redundancy ETHERNET Controller
I
= Sum of all the internal current consumption of the
(5 V) total
connected I/O modules + internal current consumption of
the fieldbus coupler/controller
I
= Sum of all the internal current consumption of the
(5 V) total
connected I/O modules at internal system supply module
5 V
=
×
(24 V)
24 V
η = 0.87
(87 % Efficiency of the power supply at nominal load 24 V)
WAGO-I/O-SYSTEM 750
I
(5 V) total
η