12.3.5.10 TCP/IP Interface (F5
The "TCP/IP Interface Object" provides for the configuration of the TCP/IP
network interface of a fieldbus coupler/controller. Examples of configurable
objects include the IP address, the network mask and the gateway address of the
fieldbus coupler/controller.
The underlying physical communications interface that is connected with the
TCP/IP interface object can be any interface supported by the TCP/IP protocol.
Examples of components that can be connected to a TCP/IP interface object
include the following: an Ethernet interface 802.3, an ATM (Asynchronous
Transfer Mode) interface or a serial interface for protocols such as PPP (Point-to-
Point Protocol).
The TCP/IP interface object provides an attribute, which is identified by the link-
specific object for the connected physical communications interface. The link-
specific object should typically provide link-specific counters as well as any link-
specific configuration attributes.
Each device must support exactly one instance of the TCP/IP interface object for
each TCP/IP-compatible communications interface. A request for access to the
first instance of the TCP/IP interface object must always refer to the instance
connected with the interface, which is used to submit the request.
Instance 0 (Class Attributes)
Table 217: TCP/IP interface (F5
Attribute ID Access
1
2
3
)

hex

) – Class
hex
Name
Get
Revision
Get
Max Instance
Get
Num Instances
Fieldbus Communication 281
Data type
Description
UINT
Revision of this object
UINT
Max. number of instances
UINT
Number of the current instanced
connections
Default
value
1 (0x0001)
2 (0x0002)
1 (0x0001),
2 (0x0002)