356 I/O Modules

Table 402: Incremental Encoder Interface Modules 750-634

Input Process Image
Offset
0
1
2
3
*)
If cycle duration measurement mode is enabled in the control byte, the cycle duration is
given as a 24-bit value that is stored in D2 together with D3/D4.
Output Process Image
Offset
0
1
2
3
750-637
The above Incremental Encoder Interface Module has a total of 6 bytes of user
data in both the Input and Output Process Image (4 bytes of encoder data and 2
bytes of control/status). The following table illustrates the Input and Output
Process Image, which have 4 words mapped into each image. Word alignment is
applied.

Table 403: Incremental Encoder Interface Modules 750-637

Input and Output Process Image
Offset
0
1
2
3
Manual
1.5.0
750-882 Media Redundancy ETHERNET Controller
Byte Destination
High Byte
-
D1
-
D4
Byte Destination
High Byte
-
D1
-
-
Byte Destination
High Byte
-
D1
-
D3
WAGO-I/O-SYSTEM 750
Low Byte
S
not used
D0
(D2) *)
not used
D3
Low Byte
C
not used
D0
-
-
Low Byte
C0/S0
Control/Status byte of Channel 1
D0
Data Value of Channel 1
C1/S1
Control/Status byte of Channel 2
D2
Data Value of Channel 2
Description
Status byte
Counter word
(Periodic time)
Latch word
Description
Control byte
Counter setting word
not used
Description