WAGO -I/O-SYSTEM 750 Manual page 291

Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-882 Media Redundancy ETHERNET Controller
Attribute ID
47 (0x2F)
100 (0x64)
101 (0x65)
102 (0x66)
103 (0x67)
104 (0x68)
105 (0x69)
Access
NV Name
Get
V
Bk_Diag_Value UINT
Set
NV Bk_FbInp_Var_
Cnt
Set
NV Bk_FbOut_Var_
Cnt
Set
NV Bk_FbInp_Plc
Only_Var_Cnt
Set
NV Bk_FbInp_Start
Plc_Var_Cnt
Set
NV Bk_FbOut_Plc
Only_Var_Cnt
Set
NV Bk_FbOut_Start
Plc_Var_Cnt
Fieldbus Communication 291
Data type Description
Contains the diagnostic byte
Note: This attribute has to be
read out before attribute 6
(DNS_i_Trmnldia), because
during the reading of attribute
6 the diagnostic byte contains
the data of the next diagnostic
UINT
Determines the number of
bytes for the PFC input
fieldbus variables, which are
added to the assembly object.
This number is added to the
consuming path. assembly
instances (101...103)
UINT
Determines the number of
bytes for the PFC output
fieldbus variables, which are
added to the assembly object.
This number is added to the
producing path. assembly
instances (104...109)
UINT
Determines the number of
bytes for the PFC input
fieldbus variables, which are
received via assembly
instance 111.
UINT
Determines starting from
which position the PFC input
fieldbus variables for the
assembly instance 111 to be
received.
UINT
Determines the number of
bytes for the PFC output
fieldbus variables, which are
received via assembly
instance 110.
UINT
Determines starting from
which position the PFC output
fieldbus variables for the
assembly instance 110 to be
received.
Default
value
0
0
0
4
0
4
0
Manual
1.5.0