WAGO-I/O-SYSTEM 750
750-882 Media Redundancy ETHERNET Controller
8.6

Restoring Factory Settings

For total deletion, first make a file system reset!
Note that you first reset the file system for the complete deletion of the controller.
Use for this the program "WAGO Ethernet Settings", as described below, and
click first on the button [Reset File System].
Then, you restore the factory settings.
To restore the factory settings, proceed as follows:
1.
Switch off the supply voltage of the fieldbus controller.
2.
Connect the communication cable 750-920 or 750-923 respectively the
Bluetooth
controller and to your computer.
3.
Switch on the supply voltage of the fieldbus controller.
4
Start the WAGO-ETHERNET-Settings program.
5.
In the top menu bar, select [Factory Settings] and click [Yes] to confirm.
A restart of the fieldbus node is implemented automatically. The start takes place
with the default settings.
®
Adapter 750-921 to the service interface of the fieldbus
Commissioning 125
Manual
1.5.0