182 Configuring via the Web-Based Management System (WBM) WAGO-I/O-SYSTEM 750

Table 50: WBM page "EtherNet/IP"

Static Assembly Instances
Entry
Pad the end of
EtherNet/IP assembly
instances 101...109 (as
required) to make an even
byte count.
Instances
Instance/Description
101
AO data & DO data
...
...
109
AI data only
110 PLC output variables
111 PLC input variables
I/O Map
Entry
Terminal 1
Terminal 2
...
Manual
1.5.0
750-882 Media Redundancy ETHERNET Controller
Default value Description
The padding of the end of EtherNet/IP assembly
instances 101...109 (as required) is activated, to
make an even byte count.
No padding of the EtherNet/IP assembly instances.
Description
Analog and digital output data
...
only analog input data
PLC output variables
PLC input variables
Example physical I/O modules
750-653/003-000
750-4xx
Data size
10 bytes
...
8 bytes
4 bytes
4 bytes
Data type and size
Input bytes 0 - 3
Output bytes 0 - 3
Input byte 8