Table 430: 2 Channel Digital Input Modules with Diagnostics and Input Process Data 75x-506
Input Process Image
Bit 7
Diagnostic bits S1/S0, S3/S2: = '00'
Diagnostic bits S1/S0, S3/S2: = '01'
Diagnostic bits S1/S0, S3/S2: = '10'
The output modules seize 4 Instances in Class (0x65).
Output Process Image
Bit 7
And the output modules seize 4 Instances in Class (0x66).
13.3.2.4

4 Channel Digital Output Modules

750-504, -516, -519, -531,
753-504, -516, -531, -540

Table 431: 4 Channel Digital Output Modules

Output Process Image
Bit 7
The output modules seize 4 Instances in Class (0x66).
13.3.2.5
4 Channel Digital Output Modules with Diagnostics and Input
Process Data
750-532
The digital output modules have a diagnostic bit for each output channel. When
an output fault condition occurs (i.e., overload, short circuit, or broken wire), a
diagnostic bit is set. The diagnostic data is mapped into the Input Process Image,
while the output control bits are in the Output Process Image.
Table 432: 4 Channel Digital Output Modules with Diagnostics and Input Process Data
Input Process Image
Bit 7
Diagnostic bit S = '0'
Diagnostic bit S = '1'
The output modules seize 4 Instances in Class (0x65).
Bit 6
Bit 5
Bit 4
Bit 6
Bit 5
Bit 4
Bit 6
Bit 5
Bit 4
Bit 6
Bit 5
Bit 4
no Error
overload, short circuit, or broken wire
Bit 3
Bit 2
Diagnostic bit
Diagnostic bit
S 3
S 2
Channel 2
Channel 2
standard mode
no connected load/short circuit against +24 V
Short circuit to ground/overload
Bit 3
Bit 2
not used
not used
Bit 3
Bit 2
controls
controls
DO 4
DO 3
Channel 4
Channel 3
Bit 3
Bit 2
Diagnostic
Diagnostic
bit
bit
S 4
S 3
Channel 4
Channel 3
I/O Modules 375
Bit 1
Bit 0
Diagnostic
Diagnostic bit
bit S 1
S 0
Channel 1
Channel 1
Bit 1
Bit 0
controls
controls
DO 2
DO 1
Channel 2
Channel 1
Bit 1
Bit 0
controls
controls
DO 2
DO 1
Channel 2
Channel 1
Bit 1
Bit 0
Diagnostic
Diagnostic bit
bit
S 1
S 2
Channel 1
Channel 2