148 Programming the PFC Using WAGO-I/O-PRO
9.6.2
Transfer via Fieldbus and ETHERNET
The physical link between the PC and the controller is set up via fieldbus. An
appropriate communication driver is required for data transfer. The driver and its
parameters must be entered in the WAGO-I/O-PRO in the dialog window
"Communication parameters".
Controller needs IP address for access!
The controller must have an IP address before it can be accessed. The operating
mode switch, which is located behind the cover of the fieldbus controller next to
the service interface, must be in the center or top position.
Start the WAGO-I/O-PRO software under Start / Programs / WAGO-I/O-
1.
PRO or by clicking the program icon on the desktop).
2.
In the menu Online select the item Communication parameters.
The dialog window "Communication parameters" then appears. The channels of
the currently connected gateway servers are shown on the left side of the
dialogue and the already installed communications drivers are shown below. This
window is empty in its default settings.
3.
Click New to set up a connection and then specify a name, e.g. TcpIp
connection.
4.
Mark the required TCP/IP driver in the right side of the dialog window to
configure the link between the PC and the controller via ETHERNET.
Use the new driver version "Tcp/Ip" (3S Tcp/Ip driver).
The following standard entries are shown in the center dialog window:
•
IP address:
•
Port number:
•
Motorolabyteorder:
•
Debug level:
5.
Change any entries as you may require.
6.
Confirm with OK.
You have now configured the TCP/IP link with the communication
parameters/drivers.
7.
Under Online, click the menu item Login to log in to the fieldbus controller
The WAGO-I/O-PRO Server is active during online operation. The
communication parameters can not be called up during this time.
Manual
1.5.0
750-882 Media Redundancy ETHERNET Controller
IP address of your controller
2455
No
16#0000
WAGO-I/O-SYSTEM 750