Table 130: Register Address 0X1000; Table 131: Register Address 0X1001 - WAGO -I/O-SYSTEM 750 Manual

Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-882 Media Redundancy ETHERNET Controller
Reading the Minimum Trigger time (Register 0x1004) reveals whether a
watchdog fault occurred. If this time value is 0, a fieldbus failure is assumed. The
timer of watchdog can manually be reset, if it is not timed out, by writing a value
of 0x1 to the register 0x1003 or to the Restart Watchdog register 0x1007.
After the watchdog is started, it can be stopped by the user via the Watchdog
Stop register (0x1005) or the Simply Stop Watchdog register (0x1008).
The watchdog registers can be addressed in the same way as described with the
MODBUS read and write function codes. Specify the respective register address
in place of the reference number.

Table 130: Register Address 0x1000

Register address 0x1000 (4096
Value
Access
Default
Description

Table 131: Register Address 0x1001

Register address 0x1001 (4097
Value
Access
Default
Description
)
dec
Watchdog time, WS_TIME
Read/write
0x0064
This register stores the watchdog timeout value as an unsigned 16 bit value. The
default value is 0. Setting this value will not trigger the watchdog. However, a
non zero value must be stored in this register before the watchdog can be
triggered. The time value is stored in multiples of 100ms (e.g., 0x0009 is .9
seconds). It is not possible to modify this value while the watchdog is running.
)
dec
Watchdog function coding mask, function code 1...16, WDFCM_1_16
Read/write
0xFFFF
Using this mask, the function codes can be set to trigger the watchdog function.
The function code can be selected via a "1"
FC 1 Bit 0
FC 2 Bit 1
FC 3 Bit 2
FC 4 Bit 3
FC 5 Bit 4
...
FC 16 Bit 15
Changes to the register value can only be made if the watchdog is deactivated.
The bit pattern stored in the register defines the function codes that trigger the
watchdog. Some function codes are not supported. For those the watchdog will
not be triggered even if another MODBUS device transmits one of them.
Fieldbus Communication 249
Manual
1.5.0