WAGO-I/O-SYSTEM 750
750-882 Media Redundancy ETHERNET Controller
13.3.3.2
2 Channel Analog Input Modules
750-452, -454, -456, -461, -462, -465, -466, -467, -469, -472, -474, -475, 476, -
477, -478, -479, -480, -481, -483, -485, -492, (and all variations),
753-452, -454, -456, -461, -465, -466, -467, -469, -472, -474, -475, 476, -477,
478, -479, -483, -492, (and all variations)
Table 438: 2 Channel Analog Input Modules
Input Process Image
Instance
n
n+1
The input modules represent 2x2 bytes and seize 2 Instances in Class (0x67).
13.3.3.3
4 Channel Analog Input Modules
750-453, -455, -457, -459, -460, -468, (and all variations),
753-453, -455, -457, -459
Table 439: 4 Channel Analog Input Modules
Input Process Image
Instance
n
n+1
n+2
n+3
The input modules represent 4x2 bytes and seize 4 Instances in Class (0x67).
13.3.3.4
4 Channel Analog Input Modules for RTD's
750-450
Table 440: 4 Channel Analog Input Modules for RTD's
Input Process Image
Instance
n
n+1
n+2
n+3
The input modules represent 4x2 bytes and seize 4 Instances in Class (0x67).
13.3.3.5
3-Phase Power Measurement Module
750-493
The above Analog Input Modules have a total of 9 bytes of user data in both the
Input and Output Process Image (6 bytes of data and 3 bytes of control/status).
The following tables illustrate the Input and Output Process Image, which has a
Byte Destination
High Byte
D1
D3
Byte Destination
High Byte
D1
D3
D5
D7
Byte Destination
High Byte
D1
D3
D5
D7
Low Byte
D0
Measured Value Channel 1
D2
Measured Value Channel 2
Low Byte
D0
Measured Value Channel 1
D2
Measured Value Channel 2
D4
Measured Value Channel 3
D6
Measured Value Channel 4
Low Byte
D0
Measured Value Channel 1
D2
Measured Value Channel 2
D4
Measured Value Channel 3
D6
Measured Value Channel 4
I/O Modules 379
Description
Description
Description
Manual