Channel Digital Input Module With Diagnostics; Channel Digital Input Module With Diagnostics And Output Process Data; Table 421: 2 Channel Digital Input Module With Diagnostics; Table 422: 2 Channel Digital Input Module With Diagnostics And Output Process - WAGO -I/O-SYSTEM 750 Manual

Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

370 I/O Modules
13.3.1.3

2 Channel Digital Input Module with Diagnostics

750-419, -421, -424, -425,
753-421, -424, -425

Table 421: 2 Channel Digital Input Module with Diagnostics

Input Process Image
Bit 7
The input modules seize 4 Instances in Class (0x65).
13.3.1.4
2 Channel Digital Input Module with Diagnostics and Output Process
Data
750-418,
753-418
The digital input module supplies a diagnostic and acknowledge bit for each input
channel. If a fault condition occurs, the diagnostic bit is set. After the fault
condition is cleared, an acknowledge bit must be set to re-activate the input. The
diagnostic data and input data bit is mapped in the Input Process Image, while
the acknowledge bit is in the Output Process Image.
Table 422: 2 Channel Digital Input Module with Diagnostics and Output Process Data
Input Process Image
Bit 7
The input modules seize 4 Instances in Class (0x65).
Output Process Image
Bit 7
And the input modules seize 4 Instances in Class (0x66).
Manual
1.5.0
750-882 Media Redundancy ETHERNET Controller
Bit 6
Bit 5
Bit 6
Bit 5
Bit 6
Bit 5
Bit 4
Bit 4
Bit 3
Diagnostic
Diagnostic
bit S 2
bit S 1
Channel 2
Channel 1
Bit 4
Bit 3
Diagnostic bit
Diagnostic bit
S 2
Channel 2
Channel 1
Bit 3
Acknowledge-
Acknowledge-
ment bit Q 2
ment bit Q 1
Channel 2
WAGO-I/O-SYSTEM 750
Bit 2
Bit 1
Bit 0
Data bit
Data bit
DI 2
DI 1
Channel 2
Channel 1
Bit 2
Bit 1
Bit 0
Data bit
Data bit
S 1
DI 2
DI 1
Channel 2
Channel 1
Bit 2
Bit 1
0
Channel 1
Bit 0
0