Page 1
WAGO I/O System 750/753 Proportional Valve Module, 2 -Channel; 24 VDC; 1.6 A 750-1632/000-100 Product manual | Version 1.1.0 /WAGO/...
Page 2
We wish to point out that the software and hardware terms as well as the trademarks of companies used and/or mentioned in the present manual are generally protected by trademark or patent. WAGO is a registered trademark of WAGO Verwaltungsgesellschaft mbH. Product manual | Version: 1.1.0 Proportional Valve Module 2-3-4...
The product must only be installed and operated in accordance with the complete operating instructions. Knowledge of all applicable documents is required for proper use. You can find all documents and information on the product detail page. Applicable document & System Manual I/O System 750/753 • Provisions • Safety • Planning •...
• Operating mode with two valves Configuration and parameterization are performed via device description files, with WAGO-I/O-CHECK or by means of function blocks. The I/O module can be used with the head stations of the WAGO I/O System 750/753 listed in the “8 Compatibility List [} 59]”...
Item number 8 Scope of Applicability [} 5] Marking possibility with Mini-WSB (op- tional) Status LEDs 8 Indicators [} 8] Data contacts & System Manual I/O System 750/753 Access to open the associated Push-in & System Manual I/O System 750/753 ® CAGE CLAMP connection ®...
Properties 750-1632/000-100 3.2 Indicators Figure 2: Indicators Name LED Description Signal state, DI 1 Signals the signal state of digital input 1 – [Unassigned] On target, channel 1 State of the actual value, channel 1 Status, channel 1 State of the output stage, channel 1 On target, channel 2...
750-1632/000-100 Properties 3.3 Wiring Interface ® Figure 3: CAGE CLAMP Connections Channel Designation Connection Function DI 1 Input, DI 1: signal voltage Sensor supply, DI 1: +24 V L1− Sensor supply, DI 1: 0 V DI 2 Input, DI 2: signal voltage Sensor supply, DI 2: +24 V L2−...
Properties 750-1632/000-100 3.4 Power Jumper Contacts The potential for the field supply is fed in via the blade contacts and passed on via the spring contacts. For additional information on the Power Jumper Contacts, please see & System Manual I/O System 750/753.
Functions 750-1632/000-100 4 Functions 4.1 Operating Modes The I/O module offers two operating modes: • Operating mode with one valve • Operating mode with two valves The operating mode of the I/O module can only be changed when the outputs stages are switched off.
750-1632/000-100 Functions 4.2 Operational Functions Depending on the parameterization of the I/O module, the following functions and proper- ties may be available: • On target • Normal operation • JOG/TIP mode • Control of functions via digital inputs • Emergency operation •...
Functions 750-1632/000-100 4.2.2 Normal Operation The control current provided by the I/O module can be directly specified in the process image (output) via a setpoint. The I/O module represents the present actual value in the process image (input) as a current value or as a percentage of the nominal current.
750-1632/000-100 Functions 4.2.3 JOG/TIP Mode In JOG/TIP mode, the valves are set manually. The actual value can only move within the valid setpoint limits. With corresponding parameterization, JOG/TIP mode can also be controlled via digital in- puts DI1 and DI2. A logical “OR” operator is applied to the digital inputs and the corre- sponding bits in the control byte.
Functions 750-1632/000-100 4.2.3.2 TIP Mode TIP mode is a time-limited variant of JOG mode. The time limit can be set via a parame- ter. Figure 8: Actual Value Curve in TIP Mode Event Description/Behavior Set SPL_EN to “0” and set TIP mode is activated. Present actual value is held.
750-1632/000-100 Functions 4.2.4 Control of Functions via Digital Inputs The following functions can be used via digital inputs DI1 and DI2 with corresponding pa- rameterization. • JOG/TIP mode • Digital input • Emergency operation • HOLD function • STOP function •...
If one of the two power supplies is interrupted, the I/O module cannot switch to emergency operation. To ensure a permanent power supply, the 750-613 I/O module can be used as the supply module, for example.
750-1632/000-100 Functions 4.2.6 HOLD Function During a ramp, the current can be held using the HOLD function. The HOLD function is controlled by means of the SPL_EN bit or, with corresponding pa- rameterization, by one of digital inputs DI1 and DI2.
Functions 750-1632/000-100 4.2.7 STOP Function With corresponding parameterization of DI 1 and DI 2, the STOP function can be trig- gered via the digital inputs. For the STOP function, the stop ramp is applied. Figure 11: Setpoint Specification for STOP Function via Digital Inputs...
750-1632/000-100 Functions 4.2.8 ENDSTOP Function The ENDSTOP function can be used to configure the reaction of the I/O module to reach- ing or exceeding a certain position or fill level, which is detected by a limit switch. The following two variants of the ENDSTOP function can be configured: •...
Functions 750-1632/000-100 4.2.8.1 End Stop Behavior in Normal Operation 4.2.8.1.1 Approaching the End Stop Value Figure 12: End Stop Behavior in Normal Operation When Approaching the End Stop Value Event Description/Behavior Set SPL_EN to “1.” Normal operation is activated. Change setpoint Ramp starts.
750-1632/000-100 Functions 4.2.8.1.2 Holding the Present Actual Value (“Freeze”) Figure 13: End Stop Behavior in Normal Operation When the Present Actual Value Is Held (“Freeze”) Event Description/Behavior Set SPL_EN to “1.” Normal operation is activated. Change setpoint Ramp starts. Present current increases with parameterized ramp.
Functions 750-1632/000-100 4.2.8.2 End Stop Behavior in JOG/TIP Mode 4.2.8.2.1 Approaching the End Stop Value Figure 14: End Stop Behavior in JOG Mode When Approaching the End Stop Value Event Description/Behavior Set SPL_EN to “0” JOG mode is activated. Present current is held.
750-1632/000-100 Functions 4.2.8.2.2 Holding the Present Actual Value (“Freeze”) Figure 15: End Stop Behavior in JOG Mode When the Present Actual Value Is Held (“Freeze”) Event Description/Behavior Set SPL_EN to “0” JOG mode is activated. Present current is held. Set JOG_POS to “1”...
Functions 750-1632/000-100 4.2.9 Substitute Value Strategy in the Event of Local Bus Failure The substitute value is output if the local bus has an error and the substitute value strat- egy has been parameterized accordingly. The substitute value strategy can be configured in such a way that either a substitute value is output or the last valid value is held.
750-1632/000-100 Functions 4.2.9.1 Holding the Actual Value If the local bus has a fault, the last valid value is held. When the fault on the local bus is cleared, the value continues to be held until this state has been acknowledged; see 8 Exiting the Substitute Value Strategy through Ac-...
Functions 750-1632/000-100 4.2.9.2 Approaching the Substitute Value The substitute value can be approached in two ways: • “Hard” approach to substitute value: There is no ramp; instead, the parameterized sub- stitute value is output directly. • “Soft” approach to substitute value: The stop ramp is used to approach the substitute value.
750-1632/000-100 Functions 4.2.9.3 Exiting the Substitute Value Strategy through Acknowledgement To exit the substitute value strategy, the fault must be eliminated, and the SPL_EN bit must be changed from 0 to 1. The acknowledgement must be performed separately for each channel. After acknowledgement, the channel is in normal operation.
Functions 750-1632/000-100 4.3 Parameter Description All I/O module parameters are listed in the following as an overview. The parameters are stored in the form of registers with a size of two bytes (one word) each. One or more reg- isters are consolidated as tables.
Functions 750-1632/000-100 Parameter Table 133 (DI 1) Table 4: Parameter Table 133 (DI 1) Register Name, Type Bits, Explanation Value/Range Description (Default) DI1_FILT, 0 ... 15 0 ... 65535 The filter is used to suppress spurious UINT Filter time (Default: 10) pulses. Input signals whose pulse length is less than the filter time are not evaluated.
750-1632/000-100 Functions Register Name, Type Bits, Explanation Value/Range Description (Default) DI2_FUNC, 0 ... 15 0 (default) Digital input UINT DI 2 function The status of DI1 is only shown in the process image, not evaluated internally. The value is inverted according to regis- ter 1.
Functions 750-1632/000-100 4.3.2 Channel-Dependent Parameters Parameter Tables 150 and 151 (Process Data Handling, Valve 1, Valve 2) Tables 150 and 151 have identical structures. As an example, Table 150 is explained here for valve 1. Table 7: Parameter Table 150 (Process Data Handling, Valve 1) Register Name, Type...
750-1632/000-100 Functions Parameter Tables 152 and 153 (Output Stage, Valve 1, Valve 2) Tables 152 and 153 have identical structures. As an example, Table 152 is explained here for valve 1. Table 8: Parameter Table 152 (Output Stage, Valve 1) Register Name, Type Bits, Explana-...
Functions 750-1632/000-100 Parameter Tables 154 and 155 (Status, Valve 1, Valve 2) Tables 154 and 155 have identical structures. As an example, Table 154 is explained here for valve 1. Table 9: Parameter Table 154 (Status, Valve 1) Register Name, Type Bits, Explana- Value/Range Description tion (Default)
750-1632/000-100 Functions Parameter Tables 156 and 157 (Ramp Generators, Valve 1, Valve 2) Tables 156 and 157 have identical structures. As an example, Table 156 is explained here for valve 1. If a value of 0 is set for the process data ramp, then the ramp function is deactivated Table 10: Parameter Table 156 (Ramp Generator, Valve 1)
Functions 750-1632/000-100 Parameter Tables 158 and 159 (Characteristic Curve Adjustment, Valve 1, Valve 2) Tables 158 and 159 have identical structures. As an example, Table 158 is explained here for valve 1. Configure all 20 supporting points if used. Overwrite unneeded supporting points with the values of the last supporting point.
Functions 750-1632/000-100 Parameter Tables 160 and 161 (Valve Adjustment, Valve 1, Valve 2) Tables 160 and 161 have identical structures. As an example, Table 160 is explained here for valve 1. Table 12: Parameter Table 60 (Valve Adjustment, Valve 1) Register Name, Type Bits, Explana- Value/Range Description...
750-1632/000-100 Functions Parameter Tables 162 and 163 (Dithering, Valve 1, Valve 2) Tables 162 and 163 have identical structures. As an example, Table 162 is explained here for valve 1. Table 13: Parameter Table 162 (Dithering, Valve 1) Register Name, Type Bits, Explana- Value/Range Description tion (Default) DG_FREQ, 0 ...
Functions 750-1632/000-100 Parameter Tables 166 and 167 (Trigger, Valve 1, Valve 2) Tables 166 and 167 have identical structures. As an example, Table 166 is explained here for valve 1. Table 14: Parameter Table 166 (Current Controller, Valve 1) Register Name, Type Bits, Explana- Value/Range Description tion...
750-1632/000-100 Functions 4.4 Signal Processing 4.4.1 Setpoint Processing 4.4.1.1 Specifying the Setpoint in the Operating Mode with One Valve Table 17: Operating Mode with One Valve Setpoint, Reference Coil Control Setpoint Range Control Value Range Coil A Coil B Valve 1 One coil, unidirec- 0 ...
Functions 750-1632/000-100 4.4.2 Overview of the Internal Signal Flow Table 20: Overview of the Internal Signal Flow Signal Explanation User setpoint Setpoint specification by the user via the process image (Vx_SETPOINT) or in JOG/TIP mode Trigger Below the adjustable trigger value, the value 0 is output.
Functions 750-1632/000-100 4.4.2.1 Trigger Function Block Figure 19: Trigger Function Block This function block is used to specify the response threshold in relation to the selected current range. If the input value is less than the parameterized threshold value, then the value 0 is output at the output.
750-1632/000-100 Functions Figure 21: Ramp Generator Four parameterizable ramps are provided for the ramp function. The respective active ramp is selected in the process output image (RSEL bits). The slope of a ramp is defined in relation to the entire range of the setpoint. This allows a setpoint jump by 100 % of the nominal value to be distributed across a parameterizable...
Functions 750-1632/000-100 Figure 23: Startup ramp: 100 % in 100 ms Figure 24: Startup ramp: 100 % in 10,000 ms Table 23: Reference Values for Ramps Activity Ramps Reference Value Normal operation Four rising and falling ramps each Nominal current JOG/TIP mode Nominal current STOP function Nominal current 4.4.2.3 Zero Point Offset Function Block...
750-1632/000-100 Functions 4.4.2.4 Linearization Function Block Figure 26: Linearization Function Block This function block is used to compensate for static nonlinearities within the connected valve. For this purpose, up to 20 supporting points can be defined by means of which the characteristic curve is gradually approximated.
Functions 750-1632/000-100 4.4.2.6 Dither Generator Function Block Figure 29: Dither Generator Function Block This function block can be used to reduce the influence of static friction. Thus even small changes in the valve position can be controlled precisely. This enables significant reduc- tions in the response threshold and hysteresis.
750-1632/000-100 Functions Using the DG_RAMP_ON and DG_RAMP_OFF parameters, the ramps can be set as percentages. Values can be specified in steps of 0.01 % of the nominal current. Using ramps avoids the problem of overshooting during a hard switch-on of the dither sig- nal, since an additional DC component is generated at this time.
Functions 750-1632/000-100 4.4.2.8 Current Measurement Function Block Figure 31: Current Measurement Function Block The current is measured via two measurement amplifiers per H-bridge, on the left and right half bridge. The parameters are fixed and cannot be changed. 4.4.2.9 Nominal Current Function Block Figure 32: Nominal Current Function Block...
750-1632/000-100 Functions 4.5 Process Image The process image depends on the type of fieldbus. 4.5.1 All Fieldbuses except PROFIBUS and PROFINET Table 25: Process Image for Operating Mode with One Valve (6 Bytes) Byte Address Input Output Byte 0 Local bus status (S0)
Functions 750-1632/000-100 4.5.3 Representation of Setpoint and Actual Value Table 29: Representation of Setpoint V1_SETPOINT, V2_SETPOINT Data type INT16 (two’s complement) Value range −100 % ... +100 % (−10000 ... +10000) Resolution 1 LSB corresponds to 0.01 % Factory settings −100 % ... +100 % of the parameterized nominal cur- rent See table Process Values –...
750-1632/000-100 Functions 4.6 Control and Status Bytes 4.6.1 Local Bus Control Byte KBUS_CTRL Table 31: Local Bus CTRL Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 REG=0 REG=1 REGCOM_DOWNSTREAM Legend 0: Register communication not active...
Functions 750-1632/000-100 4.6.3 Application Control Bytes V1_CTRL and V2_CTRL Table 33: Application Control Bytes V1_CTRL and V2_CTRL Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 JOG_POS JOG_NEG DITHER RSEL TEACH_EN SPL_EN PWR_EN Legend...
750-1632/000-100 Functions Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 PWR_EN PowerEnable: 0: Switch output stage off. 1: Switch output stage on. This bit is also used to acknowledge errors. For this purpose, the value must be changed from 1 to 0.
Functions 750-1632/000-100 4.7 Diagnostic Functions 4.7.1 Setpoint Overrange and Underrange The range for the setpoint is limited to ±100 % of the nominal current. If values outside this range are specified, then the setpoint is set to the upper or lower limiting value.
This section provides helpful information for planing the use of the product in a node. 5.1 Compatibility The I/O module can be operated on the head stations of the WAGO I/O System 750/753 listed in the following table with the specified firmware revision level or higher: Table 35: Compatibility List...
Operating tool with a 2.5 mm blade for opening the Push-in CAGE CLAMP connections 5.4 Aids You can obtain the WAGO-I/O-CHECK under Item No. ü 759-302. The description is available on the website at ü www.wago.com. WAGO e!COCKPIT is available with Item No. ü 2759-0101.
2. Left-click on the [Identify] menu item. The node configuration is determined and dis- played. ð After the node structure has been identified in WAGO-I/O-CHECK, it appears in the overview area. The start view shows the parameterization dialog for the operating modes: Figure 39: Parameterization Dialog in WAGO-I/O-CHECK...
Page 65
An overview of the adjustable parameters and their values can be found in section 8 Pa- rameter Description [} 30]. The WAGO-I/O-CHECK teach-in function is automatically executed via the “Teach-in” menu item and then, as the last step, acknowledged with a corresponding message. Diagnostics Area The diagnostics area shows the received acyclic diagnostics for Mailbox 2.0.
The following describes how to use the teach-in function for current controllers via CODESYS and e!COCKPIT. When the function is used via WAGO-I/O-CHECK, the configuration is performed auto- matically. Starting the Teach-in Function ü...
Page 67
750-1632/000-100 Commissioning Exiting the Teach-in Function • Set the TEACH_EN bit to 0. ð If the teach-in function is applied successfully, the control parameters that are deter- mined are accepted and applied. ð The TEACH_ST bit is set to 0. The LED for the channel status of the corresponding channel is switched off.
750-1632/000-100 Diagnostics 7.2 Diagnostics via Indicators Figure 40: Indicators The display elements of the I/O modules provide information about possible statuses and error cases. The tables below contain the interpretations of the signals. Table 38: LED 1 (Signal State, DI 1), LED 9 (Signal State, DI 2)
Diagnostics 750-1632/000-100 Table 42: LED 8 (Status of Field Supply Voltage) State Explanation Cause Remedy Green Field supply voltage OK – – Undervoltage Field supply undervoltage Check power supply and wiring. Table 43: LED 12 (Teach-in Function, Channel 1), LED 14 (Teach-in Function, Channel 2) State Explanation...
750-1632/000-100 Diagnostics 7.3 Diagnostics via Mailbox 2.0 The abbreviations used in the following tables have the following meanings. Table 46: Legend: Diagnostics via Mailbox – Abbreviations Abbreviation Explanation SINGLE Single event (event single shot) APPDIS Coming event/going event (event disappears/event appears)
Chan- Event Qualifier Cause of Error Corrective Action Code Mode Type APPDIS ERROR Internal error Send error report to WAGO Sup- port SINGLE ERROR ParamChn_Error GSD check 1046 SINGLE ERROR Internal input buffer full. Send error report to WAGO Sup-...
Appendix 750-1632/000-100 8 Appendix 8.1 Technology of Proportional Valves Proportional valves can be used to control the throughput of liquids or gases. The throughput is determined by a lifting armature that is pressed on the valve seat by a spring. Thus the valve is closed in its inactive state. A further component of the propor- tional valve is an electromagnet that consists of one or more coils.
750-1632/000-100 Appendix 8.1.1 Adaptation of the Valve Parameters to the Overlap Types The following three types of overlap exist: • Negative Overlap: A specified flow of the respective medium flows even in the zero position of the valve. • Zero Overlap: The valve has a defined zero position and opens very quickly.
Appendix 750-1632/000-100 8.1.2 Example Illustration of the Characteristic Curve Compensation The following illustration clarifies characteristic curve compensation by means of an ex- ample. Figure 46: Characteristic Curve Compensation In the top part of the illustration, the characteristic curve is shown for a valve with positive overlap.
Data Areas). Figure 47: Communication via Mailbox 2.0 Example: A sender wants to transfer 10 bytes (the character string “Hello WAGO”) to a receiver via a 4-byte wide channel. 8.2.1 Message The Mailbox 2.0 process packs the data into messages. A message contains a header and user data.
Appendix 750-1632/000-100 8.2.2 Transmission Channel To transfer a message over a narrow channel, synchronization between sender and re- ceiver is required. Therefore, the transmission channel is divided into a synchronization part and a data part. For synchronization, a so-called handshake byte (HB) is defined. The handshake byte oc- cupies the first byte of the transmission channel while part of the message is always de- livered in the remaining bytes.
750-1632/000-100 Appendix 8.2.3 Communication Phases The Mailbox 2.0 mechanism defines the following two communication phases: • Synchronization • Data Exchange Only after successful synchronization from sender to receiver can the actual user data be exchanged. 8.2.4 Synchronization In the synchronization phase, the handshake byte is used in Control mode. A distinction is made between interpretation as signaling mode and interpretation as command ac- knowledgment mode.
Appendix 750-1632/000-100 Signaling In signaling mode, the handshake byte appears as follows: Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Signal Table 53: Signaling Value Explanation Description 0x00 INVALID SIGNAL Status of the process image without being influenced by Mailbox 2.0...
Page 81
750-1632/000-100 Appendix 8.2.5 Data Exchange In the data exchange phase, the handshake byte is used in Toggle mode. Because a message is normally larger than the data part of the transmission channel, the message must be transferred in several cycles (fragmentation).
750-1632/000-100 Appendix 8.3 Protocols Supported by Mailbox 2.0 Messages can be exchanged between different devices using the Mailbox 2.0 transfer procedure. The respective communication partner can only understand exchanged mes- sages if they are structured in line with a known protocol. The Mailbox 2.0 transfer proce- dure uses the “Protocol ID”...
Appendix 750-1632/000-100 Service Structure of PDU (Bytes 0 … 5) Reply status: 0x00 Execution successful 0x01 Execution failed 0x02 Access denied 0x03 Table write-protected 0x04 Incorrect data length 0x05 Unknown table 0x06 Unknown register 0x07 … 0xFF (Reserved) Note Overlapping (concurrent) execution of confirmed services is prohibited A confirmed service consists of transmission of a request and receipt of a reply.
Note Subject to changes! Please also observe the further product documentation! You can generate the current ü www.wago.com datasheet at any time at: /<item number>. See also 2 Data sheet 750-1632/000-100 [} 86] Product manual | Version: 1.1.0 Proportional Valve Module 2-3-4...
Page 86
Proportional Valve Module, 2 -Channel; 24 VDC; 1.6 A The 750-1632/000-100 Proportional Valve Module controls two single-coil valves with up to 24 V/1.6 A or one valve with up to 24 V/2 A. The module features two current-con- trolled PWM* outputs with adjustable dithering.
Page 87
TIONS) Approvals for marine applications Approval Standard Certificate name DNV-CG-0339,Aug.2021 TAA00002K2 DNV Germany GmbH WAGO GmbH & Co. KG Postfach 2880 - D-32385 Minden Phone: +49(0)571/887-0 Email: info@wago.com 18.09.23 Subject to changes Hansastr. 27 - D-32423 Minden Fax: +49(0)571/887-844169 www.wago.com...
Page 88
List of Tables 750-1632/000-100 List of Tables Table 1 List of Parameter Tables....................Table 2 Parameter Table 130 (Operating Mode) ................Table 3 Parameter Table 131 (Status).................... Table 4 Parameter Table 133 (DI 1) ....................Table 5 Parameter Table 134 (DI 2) ....................Table 6 Parameter Table 140 (Additional Module Parameters)............
Page 89
750-1632/000-100 List of Tables Table 36 Accessories........................Table 37 Diagnostics via Process Image..................Table 38 LED 1 (Signal State, DI 1), LED 9 (Signal State, DI 2) ............Table 39 LED 3 (On Target Channel 1), LED 5 (On Target Channel 2) ........... Table 40 LED 4 (Status, Channel 1), LED 6 (Status, Channel 2) .............
Page 90
List of Figures 750-1632/000-100 List of Figures Figure 1 View ..........................Figure 2 Indicators ........................® Figure 3 CAGE CLAMP Connections..................Figure 4 Power Jumper Contacts ....................Figure 5 Circuit Diagram ......................Figure 6 Actual Value Curve in Normal Operation ..............
Page 91
Two Valves (3-Wire) ..................... Figure 37 One Valve (3-Wire), One Valve (2-Wire) ..............Figure 38 One Valve (2-Wire), One Valve (3-Wire) ..............Figure 39 Parameterization Dialog in WAGO-I/O-CHECK ............Figure 40 Indicators ........................Figure 41 Error Acknowledgment ....................Figure 42 Signal Flow in the Proportional Hydraulics ..............
Page 92
WAGO is a registered trademark of WAGO Verwaltungsgesellschaft mbH. Copyright – WAGO GmbH & Co. KG – All rights reserved. The content and structure of the WAGO websites, catalogs, videos and other WAGO media are subject to copyright. Distri- bution or modification of the contents of these pages and videos is prohibited. Furthermore, the content may neither be copied nor made available to third parties for commercial pur-...
Need help?
Do you have a question about the 750 and is the answer not in the manual?
Questions and answers