352 I/O Modules
750-404/000-005
The above Counter Modules have a total of 5 bytes of user data in both the Input
and Output Process Image (4 bytes of counter data and 1 byte of control/ status).
The two counter values are supplied as 16 bits. The following tables illustrate the
Input and Output Process Image, which has a total of 3 words mapped into each
image. Word alignment is applied.

Table 394: Counter Modules 750-404/000-005

Input Process Image
Offset
0
1
2
Output Process Image
Offset
0
1
2
750-638,
753-638
The above Counter Modules have a total of 6 bytes of user data in both the Input
and Output Process Image (4 bytes of counter data and 2 bytes of
control/status). The two counter values are supplied as 16 bits. The following
tables illustrate the Input and Output Process Image, which has a total of 4 words
mapped into each image. Word alignment is applied.

Table 395: Counter Modules 750-638, 753-638

Input Process Image
Offset
0
1
2
3
Output Process Image
Offset
0
1
2
3
Manual
1.5.0
750-882 Media Redundancy ETHERNET Controller
Byte Destination
High Byte
-
D1
D3
Byte Destination
High Byte
-
D1
D3
Byte Destination
High Byte
-
D1
-
D3
Byte Destination
High Byte
-
D1
-
D3
WAGO-I/O-SYSTEM 750
Low Byte
S
D0
Counter Value of Counter 1
D2
Counter Value of Counter 2
Low Byte
C
D0
Counter Setting Value of Counter 1
D2
Counter Setting Value of Counter 2
Low Byte
S0
Status byte of Counter 1
D0
Counter Value of Counter 1
S1
Status byte of Counter 2
D2
Counter Value of Counter 2
Low Byte
C0
Control byte of Counter 1
D0
Counter Setting Value of Counter 1
C1
Control byte of Counter 2
D2
Counter Setting Value of Counter 2
Description
Status byte
Description
Control byte
Description
Description