136 Programming the PFC Using WAGO-I/O-PRO
The PLC browser provides an overview of the real execution times for all
CoDeSys tasks with the command "tsk".
If in a PLC program, operating system functions are used; e.g., for the handling
of "sockets" or the "file system", these execution times are not taken into
consideration covered by the command "tsk".
CTU counter:
The CTU counter operates in a value range of 0 to 32767.
Note the maximum number of write cycles of the EEPROM!
Fieldbus couplers/controllers save some information such as IP addresses and
IP parameters in the EEPROM to make it available after a restart. The memory
cycles of an EEPROM are generally limited. Beyond a limit of approx. 1 million
write cycles, memory can no longer be assured. A defective EEPROM only
becomes apparent after a restart by software reset or power-on.
Due to a bad checksum, the fieldbus coupler/controller then always starts with
the default parameters.
The following functions use the EEPROM:
Manual
1.5.0
750-882 Media Redundancy ETHERNET Controller
WAGO-I/O-PRO
WagoLibDaylightSaving
MODBUS
Register 0x1035 Time Offset
Register 0x100B Watchdog parameters
Register 0x1028 Network configuration
Register 0x1036 Daylight saving
Register 0x1037 Modbus response delay
Register 0x2035 PI parameter
Register 0x2043 Default configuration
Parameter assignments
BootP new parameters
DHCP new parameters
WAGO MIB write access
WAGO-I/O-SYSTEM 750
SetDaylightSavings