Assigning Ip Addresses Via "Wago Ethernet Settings - WAGO -I/O-SYSTEM 750 Manual

Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

110 Commissioning
8.2.3

Assigning IP Addresses via "WAGO Ethernet Settings"

This program is used to configure an IP address to port 1 and port 2 via serial
communications interface, to reset the fieldbus coupler parameters to the factory
settings and to restore the Flash File System in which the HTML pages of the
fieldbus controller are stored.
WAGO communication cables or WAGO radio-link adapters can be used for data
communication.
Do not connect Communication Cable when energized!
To prevent damage to the communications interface, do not connect or
disconnect Communication Cable 750-920 respectively 750-923 when energized!
The fieldbus controller must be de-energized!
Set the address selection switch to 0 for active network parameter setting
via software configuration!
Set the address selection switch to 0 to disable the DIP switch and to enable the
network parameter setting of the software configuration via "WAGO Ethernet
Settings".
Restart the fieldbus node after adjusting the switch to apply the configuration
changes.
1.
Using a WAGO Communication cable 750-920 respectively 750-923,
connect your PC with the service interface of the fieldbus controller.
2.
Start "WAGO Ethernet Settings" program.
3.
Click on [Read] to read in and identify the connected fieldbus node.
4.
Select the Network tab.
5.
To assign a permanent address, select the option "Static configuration" in
the field Source (BootP is the default).
Enter the required IP Address and, if applicable, the address of the subnet
6.
mask and gateway of port 1 and port 2.
7.
Click on the [Write] button to apply the settings in the fieldbus node.
8.
You can now close "WAGO Ethernet Settings" or make other changes in
the Web-based Management System as required. To open the Web-based
Management System click on the button [WBM] on the right side.
Manual
1.5.0
750-882 Media Redundancy ETHERNET Controller
WAGO-I/O-SYSTEM 750