Pulse Width Modules; Serial Interface Modules With Alternative Data Format; Table 396: Pulse Width Modules 750-511, /Xxx-Xxx; Table 397: Serial Interface Modules With Alternative Data Format - WAGO -I/O-SYSTEM 750 Manual

Hide thumbs Also See for WAGO-I/O-SYSTEM 750:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-882 Media Redundancy ETHERNET Controller
13.2.5.2

Pulse Width Modules

750-511, (and all variations /xxx-xxx)
The above Pulse Width modules have a total of 6 bytes of user data in both the
Input and Output Process Image (4 bytes of channel data and 2 bytes of control/
status). The two channel values are supplied as 16 bits. Each channel has its
own control/status byte. The following table illustrates the Input and Output
Process Image, which has a total of 4 words mapped into each image. Word
alignment is applied.

Table 396: Pulse Width Modules 750-511, /xxx-xxx

Input and Output Process
Offset
0
1
2
3
13.2.5.3

Serial Interface Modules with Alternative Data Format

750-650, (and the variations /000-002, -004, -006, -009, -010, -011, -012, -013),
750-651, (and the variations /000-001, -002, -003),
750-653, (and the variations /000-002, -007),
753-650, -653
The process image of the / 003-000-variants depends on the parameterized
operating mode!
With the freely parameterizable variations /003 000 of the serial interface
modules, the desired operation mode can be set. Dependent on it, the process
image of these modules is then the same, as from the appropriate variation.
The above Serial Interface Modules with alternative data format have a total of 4
bytes of user data in both the Input and Output Process Image (3 bytes of serial
data and 1 byte of control/status). The following table illustrates the Input and
Output Process Image, which have a total of 2 words mapped into each image.
Word alignment is applied.

Table 397: Serial Interface Modules with Alternative Data Format

Input and Output Process Image
Offset
0
1
Byte Destination
High Byte
-
D1
-
D3
Byte Destination
High Byte
D0
D2
Low Byte
C0/S0
Control/Status byte of Channel 1
D0
Data Value of Channel 1
C1/S1
Control/Status byte of Channel 2
D2
Data Value of Channel 2
Low Byte
C/S
Data byte
D1
I/O Modules 353
Description
Description
Control/status
byte
Data bytes
Manual