Quickstart Description
Values 0 and 255 are predefined!
Set the values 0 or 255 using the address selection switch. This activates the IP
modes provided. When a value of 0 is set, the IP configurations executed by
WebBasedManagement will apply. Setting a value of 255 will activate address
allocation by DHCP.
1.
To assign a value (except for 0/255) for the host ID using the address
selection switch, you must first convert the host ID value to a binary
numeral.
In the configuration example shown here, the host ID 100 is used for the
fieldbus controller. The decimal value of "100" converts to a binary code of
"01100100."

Table 7: Binary Coding of Decimal Number 100

MSB
0
2.
Set the bits in order using the 8 DIP switches. Begin with DIP switch 1 to
set Bit 0 (LSB) and continue up to DIP switch 8 for Bit 7 (MSB).

Figure 17: Address selection switch with set IP address (192.168.1.100)

3.
Implement a restart of the fieldbus controller if you have adjusted the
address selection switch, so that the changed IP configuration will be
adopted.
To do this, open the cover for the service interface and press the mode
switch down (e.g., using an actuation tool, Item No.: 210-720).

Figure 18: Restarting the fieldbus controller via hardware reset