Configuration; Configuring The Module Via Ethernet/Ip; Selecting The Module; Selecting A Connection - WAGO TEchDocs 765-4501/0100-0000 Manual

8-port io-link master class a; ethernet/ip; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

765-4501/0100-0000

10.2 Configuration

10.2.1 Configuring the Module via EtherNet/IP

For the EtherNet/IP scanner and EtherNet/IP adapter to exchange process data, you
need to configure the EtherNet/IP scanner. This requires the device description file (EDS
file) for the module used:
• wago_07654501.eds
Carry out the following steps in the configuration software of the EtherNet/IP scanner
used:
• Import the EDS file.
• Select the module from the device catalog.
• Add the module to the configuration project.
• Select a connection: connection 1, connection 2 etc.
• Set the parameters.
The individual steps are describe in detail below.

10.2.1.1 Selecting the Module

Select the module used from the device catalog.
Module: 0765-4501/0100-0000
Designation:8 PORT IOL-A FLD EI 24 VDC 2.0 A

10.2.1.2 Selecting a Connection

The module offers multiple connections. Select a connection for your application. By se-
lecting the connection, you determine the following:
• Connection type: "Exclusive owner," "Input only" or "Listen only"
• Whether or not the scanner transfers the port parameters to the product
• Maximum amount of IO-Link process data of all connected IO-Link devices: 4, 16 or
32 bytes
Connection Type
The module offers multiple connection types:
• Input only: The scanner can only read input process data. This is the default connec-
tion type.
• Listen only: The scanner can only read input process data. This connection type re-
quires another scanner that establishes an "Input only" connection to the product.
Scanner Sends IO-Link Parameters to the Module (Only for Modules with IO-Link
Master Ports)
With "Exclusive Owner without Config" and "Listen Only" connections, the scanner does
not transfer any port parameters. For these connection types, the port parameters are set
with a different tool. You can find an overview of the tools you can use to set the port pa-
rameters under Parameterization Tools.
With "Exclusive Owner" and "Input Only" connections, the scanner transfers the port pa-
rameters to the module that you set up previously with the scanner's configuration soft-
ware. The scanner sends these parameters to the module every time a connection is es-
tablished.
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A